Parameter Reference Table - ECR International 95M-200 Parameter Manual

Gas-fired direct vent modulating hot water boiler
Table of Contents

Advertisement

Para.
Name
Storage dHW:
68° to 158°F
1
t3 Set
instantaneous
104° to 150°
dHW OFF
dHW OFF +
2
dHW System
dHW On +
CH OFF +
boiler pump
3
CH System
boiler pump
4
t1 top
120° to 194°F
5
t1 Foot
60° to 140°F
6
t4 minimum
7
t4 maximum
60° to 78°F
V - parameter Reference Table
Range
Gascom
Boiler
Software
Display
68 to 158
104 to 150
dHW:
0
dHW On
1
pump
2
constant
pump
3
constant
CH OFF
0
CH On
1
2
constant
CH On +
3
constant
68 tO 182
60 to 140
-4° to 50°
-4 to 50
60 to 78
Boiler Display
Display Position
1st
2nd
3rd
4th
1
Setting
2
Blank
Blank
Value
3
Blank
Blank
Value
4
Setting
initial reading:
P
.
0
after 2 to 3 seconds:
Blank
Setting
initial reading:
P
.
0
after 2 to 3 seconds:
Blank
Blank
Setting
initial reading:
P
.
0
after 2 to 3 seconds:
Blank
Blank
Setting
12
Description
• T3 is the DHW temperature by an immer-
sion sensor.
• DO NOT CHANGE this parameter from
the factory setting. ( Boiler outlet water
temperature setpoint in dHW mode is de-
termined by adding Parameter 1 to Param-
eter 33.)
• If applied for instantaneous DHW opera-
tion (not recommended), set Parameter 35
for the correct configuration.
• Parameter 2 determines whether DHW
heating is activated. the boiler will not op-
erate in dHW mode if this parameter is set
to "0" or "3".
• WARNING- it is not recommended to
set this parameter to either "2" or "3" (con-
tinuous dHW pump). this could result in
a hazardous condition, because it causes
constant circulation between the boiler and
the dHW heater.
• Parameter 3 determines whether the boil-
er will operate in central heating mode.
• Select "1" to cycle the boiler circulator on
central heating calls.
• Select "2" or "3" to maintain constant boil-
er circulation operation.
• Constant Boiler Temperature operation
(outside sensor not connected): t1 top is
the target outlet water temperature at all
times.
• Outside reset (outside sensor connected):
t1 top is the maximum water temperature
based on outdoor air temperature.
• T1 Foot applies only in outdoor reset op-
eration.
5
• T1 Foot is the minimum target tempera-
ture for all outside temperatures.
• T4 Minimum applies only in outdoor reset
operation.
6
• T4 Minimum is the outside temperature at
which the target outlet water temperature
is at maximum.
• T4 Maximum applies only in outdoor re-
set operation
7
• T4 Maximum is the outside temperature
at which the target outlet water tempera-
ture is at minimum.