Water Connections; Operating Precautions - Carrier Pro-Dialog Plus 30HZ Installation, Operation And Maintenance Instructions

Water-cooled/condenserless liquid chillers
Table of Contents

Advertisement

6 - WaTER CONNECTIONs

For size and position of the heat exchanger water inlet and
outlet connections refer to the certified dimensional drawings
supplied with the unit.
The water pipes must not transmit any radial or axial force
to the heat exchangers nor any vibration.
The water supply must be analysed and appropriate water
treatment elements installed: filters, additives, intermediate
heat exchangers, purges, vents, shut-off valves, etc., to prevent
corrosion, fouling and deterioration of the pump fittings.
Consult either a water treatment specialist or appropriate
literature on the subject.

6.1 - Operating precautions

The water circuit should be designed to have the least
number of elbows and horizontal pipe runs at different levels.
Below the main points to be checked for the connection:
Comply with the water inlet and outlet connections
shown on the unit.
Install manual or automatic air purge valves at all high
points in the circuit.
Use an expansion device to maintain pressure in the
circuit and install a safety valve as well as an expansion
tank.
Install thermometers in both the entering and leaving
water connections.
Install drain connections at all low points to allow the
whole circuit to be drained.
Install stop valves, close to the entering and leaving
water connections.
Use flexible connections to reduce the transmission of
vibrations.
Insulate all pipework, after testing for leaks, both to
reduce thermal leaks and to prevent condensation.
Cover the insulation with a vapour barrier.
Where there are particles in the fluid that could foul
the heat exchanger, a screen filter should be installed
ahead of the pump. The mesh size of the filter must be
1.2 mm (see 'Typical water circuit' diagram on the right).
Before the system start-up verify that the water circuits
are connected to the appropriate heat exchangers (e.g.
no reversal between evaporator and condenser).
Do not introduce any significant static or dynamic
pressure into the heat exchange circuit (with regard to
the design operating pressures).
Before any start-up verify that the heat exchange fluid
is compatible with the materials and the water circuit
coating.
In case additives or other fluids than those recommend-
ed by Carrier are used, ensure that the fluids are not
considered as a gas, and that they belong to class 2, as
defined in directive 97/23/EC.
16
Carrier recommendations on heat exchange fluids:
No NH
ammonium ions in the water, they are very
4+
detrimental for copper. This is one of the most important
factors for the operating life of copper piping. A con-
tent of several tenths of mg/l will badly corrode the
copper over time.
Cl
Chloride ions are detrimental for copper with a risk
-
of perforations by corrosion by puncture. If possible
keep below 10 mg/l.
SO
sulphate ions can cause perforating corrosion, if
2-
4
their content is above 30 mg/l.
No fluoride ions (< 0.1 mg/l).
No Fe
and Fe
ions with non negligible levels of dis-
2+
3+
solved oxygen must be present. Dissolved iron < 5 mg/l
with dissolved oxygen < 5 mg/l.
Dissolved silicon: silicon is an acid element of water
and can also lead to corrosion risks. Content < 1mg/l.
Water hardness: > 0.5 mmol/l. Values between 1 and
2.5 can be recommended. This will facilitate scale
deposit that can limit corrosion of copper. Values that
are too high can cause piping blockage over time. A
total alkalimetric titre (TAC) below 100 is desirable.
Dissolved oxygen: Any sudden change in water oxygena-
tion conditions must be avoided. It is as detrimental to
deoxygenate the water by mixing it with inert gas as it is
to over-oxygenate it by mixing it with pure oxygen. The
disturbance of the oxygenation conditions encourages
destabilisation of copper hydroxides and enlargement
of particles.
Specific resistance – electric conductivity: the higher
the specific resistance, the slower the corrosion tendency.
Values above 30 Ohm·m are desirable. A neutral
environment favours maximum specific resistance
values. For electric conductivity values in the order of
20-60 mS/m can be recommended.
pH: Ideal case pH neutral at 20-25°C
7 < pH < 8
If the water circuit must be emptied for longer than one
month, the complete circuit must be placed under nitrogen
charge to avoid any risk of corrosion by differential aeration.
Charging and removing heat exchange fluids should be done
with devices that must be included on the water circuit by
the installer. Never use the unit heat exchangers to add
heat exchange fluid.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pro-dialog plus 30hzv

Table of Contents