Electrical Data - Carrier Pro-Dialog Plus 30HZ Installation, Operation And Maintenance Instructions

Water-cooled/condenserless liquid chillers
Table of Contents

Advertisement

4.2 - Electrical data

30hZ/hZV
Power wiring
Nominal power supply
System voltage range
Control circuit power supply
Nominal operating power input*
30HZ
30HZV
Nominal operating current*
30HZ
30HZV
Maximum operating power input**
30HZ - circuit A and B
30HZ - circuit A
30HZ - circuit B
30HZV - circuit A and B
30HZV - circuit A
30HZV - circuit B
Maximum operating current (Un-10%)***
30HZ - circuit A and B
30HZ - circuit A
30HZ - circuit B
30HZV - circuit A and B
30HZV - circuit A
30HZV - circuit B
Maximum operating current (Un)***
30HZ - circuit A and B
30HZ - circuit A
30HZ - circuit B
30HZV - circuit A and B
30HZV - circuit A
30HZV - circuit B
Maximum unit starting current (Un)†
30HZ - circuit A and B
30HZ - circuit A
30HZ - circuit B
30HZV - circuit A and B
30HZV - circuit A
30HZV - circuit B
30hZ Ratio max. starting current/max. current, circ. a
30hZ Ratio max. starting current/max. current, circ. B
30hZV Ratio max. starting current/max. current, circ. a
30hZV Ratio max. starting current/max. current, circ. B
holding current for three-phase short circuits
30HZ - circuit A and B
30HZ - circuit A
30HZ - circuit B
30HZV - circuit A and B
30HZV - circuit A
30HZV - circuit B
Customer unit standby power for evaporator and condenser pump connections‡
Circuit A
Circuit B
*
Standard Eurovent conditions: Evaporator entering/leaving water temperature 12°C/7°C, condenser entering/leaving water temperature 30°C/35°C.
Nominal operating power input: unit power input (compressors, control) plus the capacity corresponding to the evaporator and condenser pressure drop (flow x drop/0.3).
**
Power input, compressors, at unit operating limits (saturated evaporating temperature (dew point) = 12°C, saturated condensing temperature (dew point) = 52°C
(30HZ)/66°C (30HZV), and a nominal voltage of 400 V (data given on the unit name plate).
*** Maximum unit operating current at maximum unit power input.
Maximum instantaneous starting current (maximum operating current of the smallest compressor(s) + locked rotor current or reduced starting current of the largest
compressor).
Current and power inputs not included in the values above.
Notes for electrical data:
30HZ/HZV 043 to 225 units have a single power connection point; 30HZ/HZV
250 to 280 units have two connection points.
The control box includes the following standard features:
-
Starter and motor protection devices for each compressor
-
Control devices
Field connections:
All connections to the system and the electrical installations must be in full
accordance with all applicable codes.
The Carrier 30HZ/HZV chillers are designed and built to ensure conformance
with local codes. The recommendations of European standard EN 60204-1
(corresponds to IEC 60204-1) (machine safety - electrical machine components
- part 1: general regulations) are specifically taken into account, when designing
the electrical equipment.
IMPORTaNT:
Conformance with EN 60204-1 is the best means of ensuring compliance with the
Machines Directive and § 1.5.1. Generally the recommendations of IEC 60364
are accepted as compliance with the requirements of the installation directives.
Annex B of EN 60204-1 describes the electrical characteristics used for the
operation of the machines.
1.
The operating environment for the 30HZ/HZV chillers is specified below:
a.
Environment* - Environment as classified in IEC 60364 § 3:
-
ambient temperature range: +5°C to +40°C, class AA4
-
humidity range (non-condensing)*: 50% relative humidity at 40°C,
90% relative humidity at 20°C
043
052
065
091
V-ph-Hz 400-3-50
V
360-440
The control circuit is supplied via a factory-installed transformer.
kW
38.5
48.9
68
69
kW
38.5
48.6
65
70
A
63.8
81.1
112
114
A
63.8
80.6
108
116
kW
45
55
77
82
kW
-
-
-
-
kW
-
-
-
-
kW
54
65
90
98
kW
-
-
-
-
kW
-
-
-
-
A
87
105
150
158
A
-
-
-
-
A
-
-
-
-
A
101
123
170
185
A
-
-
-
-
A
-
-
-
-
A
78
95
135
142
A
-
-
-
-
A
-
-
-
-
A
91
111
153
166
A
-
-
-
-
A
-
-
-
-
A
182
198
273
245
A
-
-
-
-
A
-
-
-
-
A
188
207
283
263
A
-
-
-
-
A
-
-
-
-
A
2.33
2.09
2.03
1.72
A
-
-
-
-
A
2.06
1.87
1.85
1.58
A
-
-
-
-
kA
15
15
15
15
kA
-
-
-
-
kA
-
-
-
-
kA
15
15
15
15
kA
-
-
-
-
kA
-
-
-
-
A
6
8
10
10
A
-
-
-
-
-
altitude: ≤ 2000 m
-
indoor installation*
-
presence of water: class AD2* (possibility of water droplets)
-
presence of hard solids, class AE2* (no significant dust present)
-
presence of corrosive and polluting substances, class AF1 (negligible)
-
vibration and shock, class AG2, AH2
b.
Competence of personnel, class BA4* (trained personnel - IEC 60364)
2.
Power supply frequency variation: ± 2 Hz.
3.
The neutral (N) conductor must not be connected directly to the unit (if
necessary use a transformer).
4.
Over-current protection of the power supply conductors is not provided with
the unit.
5.
The factory-installed disconnect switch(es)/circuit breaker(s) is (are) of a type
suitable for power interruption in accordance with EN 60947.
6.
The units are designed for connection to TN networks (IEC 60364). For IT net-
works the earth connection must not be at the network earth. Provide a local earth,
consult competent local organisations to complete the electrical installation.
NOTE: If particular aspects of an actual installation do not conform to the
conditions described above, or if there are other conditions which should
be considered, always contact your local Carrier representative.
*
The protection level required to conform to this class is IP21B (according to
reference document IEC 60529). All 30HZ/HZV units are protected to IP23C
and fulfil this protection condition.
101
111
121
141
161
78
86
92
112
131
77
86
94
112
135
129
142
152
185
217
127
142
156
185
224
90
100
109
132
155
-
-
-
-
-
-
-
-
-
-
107
119
130
155
180
-
-
-
-
-
-
-
-
-
-
174
192
211
255
299
-
-
-
-
-
-
-
-
-
-
203
224
246
293
340
-
-
-
-
-
-
-
-
-
-
157
173
190
230
269
-
-
-
-
-
-
-
-
-
-
182
202
221
264
306
-
-
-
-
-
-
-
-
-
-
227
275
291
330
404
-
-
-
-
-
-
-
-
-
-
251
299
318
360
436
-
-
-
-
-
-
-
-
-
-
1.45
1.59
1.53
1.44
1.50
-
-
-
-
-
1.37
1.48
1.44
1.37
1.43
-
-
-
-
-
20
20
20
20
20
-
-
-
-
-
-
-
-
-
-
20
20
20
20
20
-
-
-
-
-
-
-
-
-
-
10
10
10
12
15
-
-
-
-
-
195
225
250
280
165
201
239
270
165
200
234
266
273
333
396
448
273
332
388
441
194
232
-
-
-
-
155
155
-
-
116
155
225
270
-
-
-
-
180
180
-
-
135
180
374
449
-
-
-
-
299
299
-
-
224
299
425
509
-
-
-
-
340
340
-
-
255
340
336
404
-
-
-
-
269
269
-
-
202
269
382
458
-
-
-
-
306
306
-
-
229
306
470
536
-
-
-
-
404
404
-
-
338
404
513
589
-
-
-
-
436
436
-
-
360
436
1.40
1.33
1.50
1.50
-
-
1.68
1.50
1.34
1.28
1.43
1.43
-
-
1.57
1.43
25
25
-
-
-
-
25
25
-
-
25
25
25
25
-
-
-
-
25
25
-
-
25
25
24
32
25
32
-
-
20
20
11