10
|
Configuration
Benefit kWh power supply
Installer reference guide
214
#
Code
[9.7]
[4-04]
#
Code
[9.8.2]
[D-00]
[9.8.3]
[D-05]
Description
Water pipe freeze prevention:
▪
0: Continuous pump operation
▪
1: Non continuous pump operation
▪
2: Off
Description
Restriction: Only applicable if [9.8.4] is NOT set
to Smart grid.
Allow heater: Which heaters are allowed to
operate during preferential kWh rate power
supply?
▪
0 No: None
▪
1 Only BSH: Booster heater only
▪
2 Only BUH: Backup heater only
▪
3 All: All heaters
See also below table (Allowed heaters during
preferential kWh rate power supply).
Setting 2 is only meaningful if the preferential
kWh rate power supply is of type 1 or the hydro
module is connected to a separate normal kWh
rate power supply (via X2M/5‑6) and the backup
heater is NOT connected to the preferential kWh
rate power supply.
Restriction: Only applicable if [9.8.4] is NOT set
to Smart grid.
Allow pump:
▪
0 No: Pump is forced off
▪
1 Yes: No limitation
ERGA04~08E + EHBH/X04+08E
Daikin Altherma 3 R W
4P629085-1C – 2022.05