Product data
Product code
Product name
VG03-0006
OJL-connector 200
VG03-0031
OJL-connector 200 Blue
VG03-0032
OJL-connector 200 Green
Installation
DIN-rail and screw mounting
Type
Mounting with screw.
Max. Ø 5
Connection
Screw size
SW
1,2
Connect the input conductor when cover is open. Can be used for both copper- or aluminium
conductors. Note! The Aluminium conductor is allowed only one conductor/one space.
With the Al-conductors, it's recommended to use anti-corrosion paste. (i.e. Penetrox)
We recommend a ferrule when using a fine-stranded conductor.
Output H
1
Output H
2
The branching conductors H1 and H2 can be connected also when
the cover is closed. Note! It's allowed use only Cu-conductors for
branching.
Cross-section of conductors and number of conductors/ space. ( S / H1 / H2 )
2
2
1,5 mm
2,5 mm
-
0 / 3 / 3
Ouneva Oy
Teollisuustie 21
FI-82730 Tuupovaara, Finland
M10
Screw
Tightening torque M
1
5
SW
(M
/ M
1
s
Screw
M6
2
SW
3
2
Screw
-
Max. Input cable
3
-
SW
Max, Output cable
3
Input S
2
2
6 mm
10 mm
16 mm
0 / 2 / 2
3 / 1 / 1
3 / 1 / 1
2
70 mm
95 mm
1 / 0 / 0
Tel. +358 400 179 750
info@ouneva.fi
I
I
n Al
n Cu
160 A
200 A
160 A
200 A
160 A
200 A
DIN-rail mounting
Set the connector on DIN-rail.
Push until connector locks
down.
50-70 mm²
/ M
)
25-35 mm²
H1
H2
2,5-16 mm²
2
2
25 mm
35 mm
2 / 0 / 0
2 / 0 / 0
2
2
120 mm
150 mm
-
-
-
INSTALLATION GUIDE
U
I
n
max Al
1000 V
-
1000 V
-
1000 V
-
Removing from DIN-rail
Release the slider part with
screwdriver. Lift the
connector.
10 Nm
Stripping length (input) L
6 Nm
3 Nm
-
-
70 mm²
16 mm²
M
S
M
H2
M
H1
2
2
50 mm
The conductors number on table
1 / 0 / 0
refer only to industrially installed
terminals.
2
2
2
185 mm
240 mm
-
-
www.ounevagroup.fi
www.ounevaproducts.fi
I
U
max Cu
max
-
-
-
-
-
-
20 mm
1
12 mm
(output) L
2
L
1,2
Screw
SW
1
1
Screw
SW
2
2
2
2
300 mm
400 mm
-
-
17.1.2018