10.1 General frost protection

Value
Frost protection
temp.
*If activated, please check that a bypass has been installed.

10.2 General output regulation heating circuit

Value
Temp. difference
in flow / return line

10.3 Regulation of the mixed heating circuit

Heating modes
(mixed circuit)
Fixed value
Weather-/
outdoor
temperature-
driven mode
20
LogoTronic HIU Controller für LogoMatic G2
Adjustment range
0-inactive
1-active*
Adjustment range
Factory setting
5...50 K
5 K
Value
Mode
Fixed value
Flow line temp.
Upper support point
for outside temp.
Upper support point
Flow line temp.
Lower support point
for outside temp.
Lower support point
Factory setting
Comment
Value = 0
Refers to the entire system
(including valves for DW draw-off),
secured only via existing sensors
in the station.
Comment
Adjustment range
0-fixed value
1-weather-driven
0...100 °C
0...40 °C
30...100 °C
Factory
Comment
setting
Value = 0
+35 °C
+30 °C
Error message
if too low
+10 °C
+40 °C
Error message
if too high
-20 °C