High Limit Control - Buffalo DC319-P Assembly, Installation And Operation Instructions

Table of Contents

Advertisement

Operation

High Limit Control

Buffalo Fryers are equipped with a secondary heat control that prevents the oil temperature from rising
above 195°C/450°F. (Because of the accuracy tolerance of the sensor, the oil temperature may reach as
high as 200°C/475°F.)
In the event the fryer shuts down due to this condition, the oil must be cooled to below 185°C/400°F
before the pilot burner can be re-ignited. When the oil has cooled, use the "Lighting" procedure on page
10 to place the fryer back in operation. If the problem persists, contact our Buffalo Service Representative
or the Buffalo Service Department.
Main burner air supply:
1. For efficient burner operation, a proper balance of gas volume and primary air supply must be main-
tained which will result in complete combustion. Insufficient air supply results in a yellow streaming
flame. Primary air supply is controlled by an air shutter on the front of the burner.
2. Loosen the screws on the front of the burner and adjust the air shutter to just eliminate the yellow
tips of the burner flame. Lock the air shutter in place by tightening the screws.
CAUTION
The space between the castors at the bottom admits combustion air. DO NOT BLOCK THIS SPACE.
All burners are lit from constantly burning pilots. Turning the valve to the desired is all that is required
to put the unit in service.
Do not permit fans to blow directly at the unit. Wherever possible, avoid open windows next to the
units' sides or back. Avoid wall type fans which create air cross-currents within a room.
It is also necessary that sufficient air should be allowed to enter the room to compensate for the
amount of air removed by any ventilating system. Otherwise, a subnormal atmospheric pressure will
occur, affecting operation and causing undesirable working conditions.
A properly designed and installed hood will act as the heart of the ventilating system for the room or
area in which the unit is installed, and will leave the unit independent of changing draft conditions.
The Combination Valve must be checked periodically. This must be done by an authorized service rep-
resentative in your area.
Note:
Please wait at least 15 seconds to restart the main burners to maintain the best function of the thermostat
valve after turning off the main burners.
Should any abnormal operation like;
- ignition problems,
- abnormal burner flame,
- burner control problems,
- partial or full loss of burner flame in normal operation,
be noticed, the appliance requires IMMEDIATE service by a qualified service person and should not be
used until such service is carried out.
IMPORTANT
12

Advertisement

Table of Contents
loading

This manual is also suitable for:

Dc319-n

Table of Contents