SPX Cooling Technologies Marley MH 05-116E User Manual page 19

Fluid cooler
Table of Contents

Advertisement

Caution
Operation
Coil Volume
Model
US Gallons
MHF702__061
MHF702__081
MHF702__101
MHF702__121
MHF702__062
MHF702__082
MHF702__102
MHF702__122
MHF703__061
MHF703__081
MHF703__101
MHF703__121
MHF703__062
MHF703__082
MHF703__102
MHF703__122
MHF704__061
MHF704__081
MHF704__101
MHF704__121
MHF704__062
MHF704__082
MHF704__102
MHF704__122
When the use of industrial antifreeze solutions is not possible, the system
must be operated to meet both of the following conditions.
1. Maintain sufficient flow rate through the coil.
2. Maintain sufficient heat load on the process fluid. Fluid exiting the
coil must be maintained at or above 45°F. Cycling of the recirculation
pump should not be used to control process temperatures.
Draining the coil is not acceptable as a normal method of freeze
protection—draining promotes corrosion inside the coil tubes. Drain-
ing is acceptable in an emergency if the coil is not protected by an
antifreeze solution.
It is recommended that you discuss your freeze prevention options with
your local Marley sales representative.
Model
65
MHF705__061
85
MHF705__081
105
MHF705__101
125
MHF705__121
75
MHF705__062
100
MHF705__082
120
MHF705__102
150
MHF705__122
85
MHF706__061
115
MHF706__081
140
MHF706__101
170
MHF706__121
100
MHF706__062
130
MHF706__082
165
MHF706__102
200
MHF706__122
160
MHF707__061
210
MHF707__081
260
MHF707__101
310
MHF707__121
190
MHF707__062
250
MHF707__082
315
MHF707__102
375
MHF707__122
Coil Volume
US Gallons
235
315
390
465
285
380
470
565
390
500
610
725
475
610
750
885
450
580
710
840
570
740
905
1071
19