Mitsubishi Electric PUD-SWM60VAA Service Manual page 38

Air to water heat pump units
Hide thumbs Also See for PUD-SWM60VAA:
Table of Contents

Advertisement

<Thermistor feature chart>
Low temperature thermistors
• Thermistor <Liquid> (TH3)
• Thermistor <2-phase pipe> (TH6)
• Thermistor <Ambient> (TH7)
• Thermistor <Suction> (TH32)
Thermistor R0 = 15 k" ± 3 %
B constant = 3480 ± 1 %
1
1
=15exp{3480( 273+t – 273 )}
R
t
0 °C
15 k"
30°C
10 °C
9.6 k"
40°C
20 °C
6.3 k"
25 °C
5.2 k"
Medium temperature thermistor
• Thermistor <Heat sink> (TH8)
Thermistor R50 = 17 k" ± 2 %
B constant = 4150 ± 3 %
1
1
=17exp{4150( 273+t – 323 )}
R
t
0 °C 180 k"
25 °C
50 k"
50 °C
17 k"
70 °C
8 k"
90 °C
4 k"
High temperature thermistors
• Thermistor <Discharge> (TH4)
• Thermistor <Comp. surface> (TH33)
Thermistor R120 = 7.465 k" ± 2 %
B constant = 4057 ± 2 %
1
=7.465exp{4057( 273+t – 393 )}
R
t
20 °C
250 k"
70 °C
30 °C
160 k"
80 °C
40 °C
104 k"
90 °C
50 °C
70 k"
100 °C
60 °C
48 k"
110 °C
OCH756
4.3 k"
3.0 k"
1
34 k"
24 k"
17.5 k"
13.0 k"
9.8 k"
50
40
30
20
10
0
-20 -10 0 10 20 30 40 50
Temperature (°C)
200
150
100
50
0
25
Temperature (°C)
500
400
300
200
100
0
25
Temperature (°C)
38
50
75
100
125
50
75
100
120

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents