Vaillant ecoTEC plus VU 446/5-5 (H-GB) Installation And Maintenance Instructions Manual page 56

Hide thumbs Also See for ecoTEC plus VU 446/5-5 (H-GB):
Table of Contents

Advertisement

Code
Parameter
D.017
Heating control type
D.018
Pump mode setting
D.020
Max. set value for target cylinder
value
D.022
Domestic hot water demand
D.023
Heating demand
D.024
Status of the air pressure monitor
D.025
Domestic hot water generation en-
abled by eBUS control
D.026
Control of the optional grey relay
X16
D.027
Switching accessory relay 1 for 2 in
7 multi-functional module accessory
D.028
Switching accessory relay 2 for 2 in
7 multi-functional module accessory
D.029
Heating flow (heating circuit or cylin-
der charging)
D.033
Fan speed target value
D.034
Fan speed actual value
D.035
Position of the prioritising diverter
valve
D.040
Flow temperature
D.041
Return temperature
D.044
Digitised ionisation value
D.047
Outdoor temperature (with weather-
compensated control)
D.050
Offset for minimum speed
56
Values or explanations
0 = Flow temperature control
1 = Return temperature control
1 = Comfort (continuously operating pump)
3 = Eco (intermittently operating pump)
50 to 65 ℃
0 = Off
1 = on
0 = Off
1 = on
0 = open
1 = closed
0 = No
1 = Yes
1 = Circulation pump
2 = External pump
3 = Cylinder charging pump
4 = Smoke flap
5 = External solenoid valve
6 = External fault message
7 = Solar pump (not active)
8 = eBUS remote control (not active)
9 = Anti-legionella pump (not activated)
10 = Solar valve (not active)
1 = Circulation pump
2 = External pump
3 = Cylinder charging pump (not activated)
4 = Smoke flap
5 = External solenoid valve
6 = External fault message
7 = Solar pump (not active)
8 = eBUS remote control (not active)
9 = Anti-legionella pump (not activated)
1 = Circulation pump
2 = External pump
3 = Cylinder charging pump (not activated)
4 = Smoke flap
5 = External solenoid valve
6 = External fault message
7 = Solar pump (not active)
8 = eBUS remote control (not active)
9 = Anti-legionella pump (not activated)
l/min
rpm
rpm
Not connect.
Actual value in °C
Actual value in °C
0 to 1,020
Good flame < 400
No flame > 800
Actual value in °C if an outdoor temperature sensor is
connected to X41
0 to 3,000 rpm
Installation and maintenance instructions ecoTEC plus 0020261389_03
Default
User-spe-
setting
cific setting
0
3
65 ℃
Not ad-
justable
Not ad-
justable
Not ad-
justable
2
1
2
Not ad-
justable
Not ad-
justable
Not ad-
justable
Not ad-
justable
Not ad-
justable
Not ad-
justable
Not ad-
justable
Not ad-
justable
30

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ecotec plus vu 606/5-5 (h-gb)

Table of Contents