B Overview Of Diagnostics Codes - Vaillant ecoTEC plus VU 446/5-5 (H-GB) Installation And Maintenance Instructions Manual

Hide thumbs Also See for ecoTEC plus VU 446/5-5 (H-GB):
Table of Contents

Advertisement

#
Maintenance work
28
Reassemble the product
29
Opening the service valves
30
Test that the product/heating installation and the domestic hot water gen-
eration (if required) are working correctly. If required, carry out purging
31
Checking and, if required, correcting the position of the frost protection
heating elements
32
Completing inspection and maintenance work
33
Visually check the ignition and burner behaviour
34
Checking the CO/CO₂ content following maintenance work
35
Check the product for gas, flue gas and water leaks
B
Overview of diagnostics codes
Validity: VU 446/5-5 (H-GB) OR VU 606/5-5 (H-GB)
Note
Since the code table is used for various products, some codes may not be visible for the product in question.
Code
Parameter
D.000
Partial heat load
D.001
Overrun time for the internal pump
after a heat demand
D.002
Max. burner anti-cycling time in heat-
ing mode at 20 °C flow temperature
D.003
Domestic hot water temperature
D.004
Measured value for the cylinder
temperature in °C
D.005
Target value for the heating flow
temperature (or target value for the
return) in °C
D.007
Target value for the domestic hot
water cylinder temperature in °C
D.009
Heating flow temperature, target
value from external eBUS controller
D.010
Status of the internal heating pump
D.011
Status of additional external heating
pump
D.012
Status of cylinder charging pump
D.013
Status of circulation pump
D.014
Setting for speed-controlled internal
heating pump
D.015
Current speed of the internal heating
pump in %
D.016
24 V DC room thermostat
open/closed
0020261389_03 ecoTEC plus Installation and maintenance instructions
Values or explanations
Adjustable partial heat load in kW
Auto: The product automatically adjusts the maximum
partial load to the current system demand.
2 to 60 min
2 to 60 min
Not connect.
If a domestic hot water cylinder with sensor is connec-
ted
The current target value, maximum value of the para-
meter that is set for D.071, limitation by an eBUS con-
trol, if connected
(15 °C = frost protection, 40 °C up to D.020 (max.
70 °C))
0 = Off
1 = On
0 = Off
1-100 = On
0 = Off
1-100 = On
0 = Off
1-100 = On
0 = auto (pump modulates in accordance with the
control, with constant pressure)
From 1 to 5 = Fixed pump setting
1 = 53%
2 = 60%
3 = 70%
4 = 85%
5 = 100%
Heating mode off/on
Interval
After each time maintenance
work is carried out
Annually
Annually
Annually
Annually
Annually
Annually
Annually
Default
setting
Auto
5 min
20 min
0
47
User-spe-
cific setting
Not ad-
justable
Not ad-
justable
Not ad-
justable
Not ad-
justable
Not ad-
justable
Not ad-
justable
Not ad-
justable
Not ad-
justable
Not ad-
justable
55