6. Specifications

MODEL NUMBER
CAPACITY
Power rating
INPUT
OUTPUT
Voltage
Waveform
Frequency
Efficiency
Overload Capacity
BATTERY
Cell type
Cell Configuration
Charger voltage
Charger current
Recharge time
Dimensions
PHYSICAL
(W x D x H)
Weight
Line cord
Receptacles
Operating
ENVIRONMENT
temperature
Altitude
APPROVALS
WARRANTY
COMMUNICATIONS INTERFACE
INCLUDED IN BOX
Note: *Depending on load level. **Derate capacity to 80% when the output voltage is adjusted to 100VAC.
***Rack depth is front bracket to unit panel. Add 1" for depth including front bezel.
CPI User Manual for Lithium Ion Online UPS
120VAC, 2U Lithium Ion Online UPS
LD1500A
1500VA (1350W)
55–150VAC* / 50/60Hz auto-sensing
100**/110/115/120/127 Vac selectable
<=2% THD (linear load), <=4% THD (non-linear load)
> 110% & ? 130% for 5 min; > 130% & ?140% for 30 sec; >140% for 1.5 sec
LFP26650 2600 mAh
15S2P
52.5VDC
1/2/4/6/8A(max.), adjustable through LCD
1.5 hours recover to 90% capacity
17.2 x 15.1 x 3.5***
25.6 lbs
6 ft, 5–15P
(8) NEMA 5-15R
32–104°F (0 ~ 40°C)
11,500 ft above sea level
UL, cUL, RoHS, FCC Class A, battery packs comply to UL1973
6 years electronics, 6 years battery warranty (USA and Canada)
RS-232, USB, EPO, intelligent slot for optional cards (Web/SNMP)
Software, horizontal brackets, tower pedestals, user manual
04/22v.1
LD2000A
2000VA (1800W)
50/60Hz +/-0.1Hz
Up to 98%
(15S2P) x 2
17.2 x 19 x 3.5***
17.2 x 23.8 x 3.5***
33.5 lbs
6 ft, 5–20P
(8) NEMA 5–15/20R
L5–30R+(6)5–15/20R
LD3000A
3000VA (2700W)
(24S1P) x 3
84VDC
45.2 lbs
6 ft, L5–30P
Page 25