Repairs And Replacement; Maintenance Schedule - Baso B Series Installation Instructions Manual

Automatic pilot gas valve

Advertisement

Repairs and Replacement

!
WARNING: Risk of Explosion or Fire.
Shut off the gas supply at the main manual shutoff
valve before installing or servicing the G92. Failure
to shut off the gas supply can result in the release of
gas during installation or servicing, which can lead to
an explosion or fire, and may result in severe
personal injury or death.
!
CAUTION: Risk of Electrical Shock.
Disconnect power supply before making electrical
connections to avoid electrical shock.
!
WARNING: Risk of Explosion, Fire, or
Electrical Shock.
Label all wires before they are disconnected when
replacing the G92. Wiring errors can cause improper
or dangerous operation and may result in an
explosion, fire, or electrical shock leading to severe
personal injury or death.
Figure 8: SVC200 Wire Connect
DIN Type Connector
Figure 9: SVC210 Conduit 1/2 NPT
DIN Type Connector
©
2018 BASO Gas Products
Part No. BASO-INS-G92MODELREVB, Rev. -
G92 Model Rev. B Series BASOTROL® Automatic Pilot Gas Valve

Maintenance Schedule

Preventive maintenance programs are an important
part of maintaining optimum and safe function of your
BASO products. Commercial cooking and other
heating equipment can be a heavy cycling demand on
gas safety controls.
The maintenance programs should include frequent
checkout of the gas controls. Review the procedure as
described in the setup and adjustments and check for
leakage section of the instructions.
Exposure to water, chemicals, dirt, heat and grease
can all contribute to premature shut down of the gas
controls.
The frequency of the maintenance must be determined
by the appliance manufacturer where the controls are
installed and the end user for each individual
application.
Things to consider when determining a preventive
maintenance program:
Number of cycles a gas control will see
annually (more than 20,000 cycles). The gas
control should be checked monthly.
Gas controls used less than 20,000 cycles
should be checked before every shutdown and
restart process.
Heavy grease, high heat, wash down
exposure, corrosive environment areas should
be checked with a higher frequency to prevent
premature shutdown from rapid deterioration.
Simply doing a scheduled maintenance program will
help remove the chances of a costly unexpected
shutdown.
Field repairs must not be made to the G92 Series
valve as this will void the manufactures warranty.
Never try to replace a gas control unless you are a
authorized licensed gas contractor. In all cases, use
an authorized licensed gas contractor for any gas
control replacement.