Maintenance And Testing; Maintenance; Testing - Simplex 4098 Manual

Hide thumbs Also See for 4098:
Table of Contents

Advertisement

Sensors
Compatible bases
4098-9733
4098-9775
4098-9778
4098-9776
4098-9777
4098-9780
4098-9733
5
4098-9772
4098-9778
5
4098-9794
8
4098-9734
5, 7
4098-9771
5, 7
4098-9773
4098-9775
6
4098-9714
4098-9776
4098-9764
4098-9780
4098-9774
4098-9792
4098-9789
4098-9791
4098-9747
4098-9770
5
4098-9771
5
4098-9773
Note:
1.
For detailed interconnection data, see the wiring diagrams for the specific panels.
2.
The panel compatibility identification marker is the model number of the module or panel.
3.
The sensor compatibility identification marker is the model number found on the sensor label.
4.
The 4098-9764 sensor is NOT compatible with bases that have a RED DOT located in the sensor mounting area.
5.
The maximum quantity of 4098-9772, 4098-9794 Sounder Bases and 4098-9771 and 4098-9773 CO Sounder bases when the
output is coded using MAPNET II/ IDNet control (Temporal Code) is 43. If the coding is performed using 24 VDC or NAC circuit,
use the limits specified in Table 12.
6.
The 4098-9714 sensor must be used with IDNet 2 Software version 2.02.02 or later.
7.
The 4098-9770, 4098-9771, and 4098-9773 CO Bases are compatible with IDNet on the 4100U, 4100ES, 4010ES, and 4007ES
only.
8.
The 4098-9734 Heat Sensor is compatible with IDNet on the 4100ES, 4010ES, and 4007ES only.
9.
Compatible with IDNet2 only.
6.3

Maintenance and testing

6.3.1

Maintenance

The minimal requirement for detector and sensor maintenance requires clearing of surface dust using a vacuum cleaner. Ensure that the
cleaning programs comply with the NFPA and local environments. Ensure that cleaning of the internal chamber is only done by a qualified
technical representative.
For service, return to your local branch office.
6.3.2

Testing

Smoke sensor sensitivities are set and continuously monitored by the control unit. Dirty or out-of-range sensors are annunciated by the
control unit. This functionality complies with NFPA 72.
page 35
Table 12: 4098 Sensor and Sensor Base compatibility
Max. quantity of devices on a circuit
4098-9789
IDNET:
4098-9791
200 (4008)
4098-9792
Addresses 1-200
4098-9793
MAPNET II:
127 (4020), 127 (4100+), 127 (4100U), 127 (4100ES), 127 (4120)
Addresses 1-127
IDNET:
250 (4010), 250(4100U), 250 (4100ES), 250 (4010ES, 4007ES)
Addresses 1-250
IDNET 2:
5
4098-9772
250 (4100ES), 250 (4010ES, 4007ES)
5
4098-9794
Addresses 1-250
4098-9770
5
4098-9771
5
4098-9773
4098-9777
4098-9793
9
4098-9766
9
4098-9767
IDNET:
250 (4100U), 250 (4100ES), 250 (4010ES, 4007ES)
Addresses 1-250
4098 Detectors, Sensors, and Bases Application Manual