4098 Bases; Mounting - Simplex 4098 Manual

Hide thumbs Also See for 4098:
Table of Contents

Advertisement

Detector Model
4098-9612 (UL)
4098-9613 (UL)
4098-9614 (UL)
4098-9615 (UL)
4098-9616E
4098-9617E
4098-9618E
4098-9619E
4098-9621E
4098-9622E
4098-9624E
4098-9625E
4098-9626E
4098-9627E
4098-9628E
4098-9629E
4098-9630E
4098-9631E
* RR abbreviates Rate-of-Rise; FT abbreviates Fixed-Temperature.
All heat detectors identified in the following table mount to a detector base, refer to
in

Mounting

when mounting detector bases.
Product ID
Description
4098-9612
Fixed-Temp. Only, 135°F
(57°C)
4098-9613
Fixed-Temp. and Rate-of-
Rise, 135°F (57°C)
4098-9614
Fixed-Temp. Only, 200°F
(93°C)
4098-9615
Fixed-Temp. and Rate-of-
Rise, 200°F (93°C)
3.3

4098 Bases

The 4098-9788 base is designed for use with the 4098 Series smoke and heat detectors. To use a 4 wire configuration, you must use the
4098-9682 relay base. Heat detectors require the 4098-9684 base when used with a remote LED. This section only covers the information
necessary for mounting and wiring these base configurations. Before installing these bases, make a survey of the area to be covered in
accordance with the information provided in NFPA 72. For additional information, refer to the NEMA Guide for Proper Use of System Smoke
Detectors.
CAUTION: Install the bases in this section in accordance with applicable NFPA standards, local codes, and Authorities Having Jurisdiction
(AHJs). Failure to follow these instructions can result in the detector failing to initiate an alarm condition. The manufacturer is not
responsible for detectors that have been incorrectly installed, tested, or maintained.
3.3.1
Mounting
The 4098-9788 base mounts to the following electrical boxes:
• A 4 inch, or 10.16 centimeter octagonal electrical box.
• A 4 inch, or 10.16 centimeter square electrical box.
• A single gang electrical box.
Use the 4098-9832 adapter plate kit when mounting to a 4 inch square or any surface mounted box.
page 12
Table 3: Heat detector models and features
Rating or Class*
135°F (57°C) FT
135°F (57°C) FT and RR
200°F (93°C) FT
200°F (93°C) FT and RR
A1
C
A
B
D
I
134°F (56.7°C) FT
134°F (56.7°C) FT and RR
134°F (56.7°C) FT
134°F (56.7°C) FT and RR
190°F (87.8°C) FT
190°F (87.8°C) FT and RR
190°F (87.8°C) FT
190°F (87.8°C) FT and RR
Table 4: Heat detector specifications
Application
Unusually violent temp. fluctuations and ceiling
temperatures not exceeding 100°F (38°C)
Normal temp. fluctuations and ceiling
temperatures not exceeding 100°F (38°C)
Unusually violent temp. fluctuations and ceiling
temperatures exceeding 100°F (38°C) but not
150° F (68°C)
Normal temp. fluctuations and ceiling
temperatures exceeding 100°F (38°C) but not
150°F (68°C)
4098 Detectors, Sensors, and Bases Application Manual
Area / Language
English
English
English
English
European
European
Australian
Australian
Australian
Chinese
Korean
Korean
Taiwanese
Taiwanese
Korean
Korean
Taiwanese
Taiwanese
4098 Bases
for more information. Use the information
Max. Spacing
Allowed (UL)
70 X 70 ft. (21 X 21
m)
70 X 70 ft (21 X 21
m)
70 X 70 ft.(21 X 21
m)
70 X 70 ft.(21 X 21
m)
Color Code
White
White
Green
Red
White
Blue
Red
Green
FM
RTI = Quick 20 X 20 ft.
(6.1 X 6.1 m)
RTI = Quick 20 X 20 ft
(6.1 X 6.1 m)
RTI = Quick 20 X 20 ft.
(6.1 X 6.1 m)
RTI = Ultra Fast 50 X
50 ft.(15.2 X 15.2 m)
574-709 Rev. AP