5.3

4098-9822 Relay Module wiring

The 4098-9822 Relay Module is used with the 4098-9771 through 4098-9773, 4098-9775, 4098-9780, 4098-9789, 4098-9791 and
4098-9794 Sensor Bases. Install the relay module using Figure 14 and Figure 22 as a reference.
Important:
Do not use a remote LED when using the 4098-9822 relay module. The 4098-9822 relay module is not supervised and can only be used
for non-critical supplementary functions. There is a limit of ten control outputs activated on a MAPNET II/IDNet channel. If the channel
capacity is exceeded, the relay module can fail to function correctly.
Note:
1.
Do not use a remote LED.
2.
18 VDC to 32 VDC, 0.008 A typical / 0.013 A maximum.
3.
Contact A or B: Dry, Form "C" - each rated 2 A resistive at 24 VDC / 0.5 A at 110 VAC, resistive.
4.
Contact A from 4098-9771, 4098-9772, 4098-9773, 4098-9775, 4098-9780, 4098-9789, 4098-9791 or 4098-9794 sensor base.
5.4

Relay Module installation

To install the relay module complete the following steps:
1.
Mount a 1-1/2 inch, or 3.81 centimeter extension ring, that is not supplied, to an octagonal or square electrical box, also not
supplied. The extension ring is required to meet the minimum box volume requirement of 32.3 cubic inches, or 529.4 cubic
centimeters for relay module installation.
2.
Mount the relay module inside the extension ring directly behind the base and sensor. Do not mount it remotely. See Figure 20
or Figure 22 for the relay module connections.
Note: Use the exact configuration of electrical box, square or octagonal, with an extension to mount the sensor base, when installing the
relay module.
page 32
Figure 22: 4098-9822 Relay Module wiring
4098 Detectors, Sensors, and Bases Application Manual
574-709 Rev. AP