Conductive Level Switch model: LNK-K 4. Regulation Use Any use of the Conductive Level Switch, model: LNK-K, which exceeds the manufacturer’s specification, may invalidate its warranty. Therefore, any resulting damage is not the responsibility of the manufacturer. The user assumes all risk for such usage.
5.1. External electrode relay (e.g. NE-104, 304) When the LNK-K is used as a 1-stem probe, the evaluation can take place with an external electrode relay. For connection and adjustment please see instruction manual of the external electrode relay.
Please avoid screwing in and unscrewing the sensor from the sleeve, because on high stress the sealing edge can distort and the process connection can get leaky. The sealing system is designed for CIP- and SIP-cleaning. LNK-K K06/0422 Page 5...
LNK-K 6.2. Installation in G1/2 thread If the sleeve LZE is not used for the installation of the level switch LNK-K, it is possible to seal the screw thread with an adequate sealing material. Thus an installation is possible in a pipe as well as in a vessel.
4 not connected 7.2. Plug assignment of M12-plug with switching electronics 1 Power Supply + Vs / GND 2 Sensitivity + Vs / GND / open 3 Power Supply GND / +Vs 4 Output: Transistor PNP LNK-K K06/0422 Page 7...
Page 8
2. Cover probe with the medium to be measured. 3. If the output does not switch, try steps 2 and3 in succession. Step Sensitivity Plug PIN 2 2 k open (not connected) 20 k 200 k Page 8 LNK-K K06/0422...
LNK-K 9. Order Codes Example order: LNK-K 2 0 A 00S Electrode Electrode Electrode Electrical connection Model Design material coating length Evaluation A = 4 mm stump 00S = without electronics, 0 = without B = 100 mm M12x1-Stecker, coating...
LNK-K 12. EU Declaration of Conformance We, KOBOLD-Messring GmbH, Hofheim-Ts, Germany, declare under our sole responsibility that the product: Conductive Level Switch Model: LNK-K to which this declaration relates is in conformity with the standards noted below: EN 61326-1: 2013...