NOTE: The MDL Module is factory set with the sync error
contacts in the open state. These contacts may close during
shipping. Approximately two seconds after power-up, these
contacts will open.
NOTE: This contact could be wired to a separate monitor-
ing input at FACP.
Figure 3:
NOTE: If zone 1 output of module is connected to strobes,
chime/strobes or horn/strobes, zone 1 input supply power
must be continuous for proper operation.
MASTER MODULE
HORN
(+)
CONTROL
(–)
FACP
ZONE 1
(+)
NAC1
IN
(–)
ZONE 2
NAC2
(+)
(–)
IN
SLAVE
(+)
(–)
IN
Temp. Jumper Off
SLAVE MODULE
HORN
(+)
(–)
CONTROL
)
( +
ZONE 1
(+)
NAC3 OUT
(–)
IN
)
( –
STYLE Z
(CLASS A)
)
( +
ZONE 2
(+)
NAC4 RETURN
IN
(–)
)
( –
SLAVE
(+)
IN
(–)
Temp. Jumper Off
NOTE: The panel (or FACP) must be capable of providing Style Z (Class A)
notification (or NAC) circuitry. Consult with panel manufacturer.
Figure 4: Multiple Devices Using Sync Error
NOTE: If zone 1 output of module is connected to strobes,
chime/strobes or horn/strobes, zone 1 input supply power
must be continuous for proper operation.
FACP
(+)
NAC1
(–)
(+)
NAC2
(–)
(+)
(–)
TEMP. JUMPER OFF
SEPARATE
MONITORING
INPUT
(+)
NAC3
(–)
(+)
NAC4
(–)
(+)
(–)
TEMP. JUMPER OFF
D900-14-00
)
( +
ZONE 1
(+)
OUT
(–)
TO NEXT
DEVICE OR
EOL
ZONE 2
)
( +
OUT
)
( –
)
( –
2 STYLE Y (CLASS B)
)
( +
SYNC
)
( +
ERROR
)
( –
TO NEXT
DEVICE OR
EOL
SLAVE
)
( +
)
( –
OUT
)
( –
All SpectrAlert horns,
horn/strobes, and strobe
only devices will
operate in sync.
)
( +
ZONE 1
(+)
OUT
(–)
TO NEXT
DEVICE OR
EOL
ZONE 2
)
( +
OUT
)
( –
)
( –
1 STYLE Z (CLASS A)
)
( +
SYNC
)
( +
ERROR
)
( –
TO NEXT
DEVICE OR
EOL
SLAVE
)
( +
OUT
)
( –
)
( –
MODULE 1
HORN
ZONE 1
)
( +
CONTROL
)
( –
OUT
ZONE 1
ZONE 2
)
( +
IN
OUT
)
( –
ZONE 2
SYNC
)
( +
IN
ERROR
)
( –
SLAVE
SLAVE
)
( +
IN
OUT
)
( –
MODULE 2
HORN
ZONE 1
)
( +
CONTROL
OUT
)
( –
ZONE 1
ZONE 2
)
( +
IN
OUT
)
( –
ZONE 2
SYNC
)
( +
EOL
IN
ERROR
)
( –
SLAVE
SLAVE
)
( +
OUT
IN
)
( –
firealarmresources.com
Figure 5: Wiring for Coded Supplies
MULTI CODE
SOURCE
MDL
HC
Z1
IN
OUT
NOTE: Horn/chime control must be powered for horn/
strobes to operate the horn portion.
NOTE: SpectrAlert horn-only/chime-only and horn/strobe
or chime/strobe devices must be set non-temporal for
multi-code sourcing.
Temporal Coding on horns that produce a continuous
tone (Non-SpectrAlert Horns)
See Figure 6
• Program module to provide temporal coding by inserting
jumper plug per instructions.
• Connect only sounders producing a continuous tone to
the module zone output(s).
Strobes cannot be used on a module providing temporal coding
to horns. Strobes must be wired for independent operation.
A0181-00
NOTE: Temporal jumper should be inserted across both
pins only on non-SpectrAlert products that are to be pow-
ered for temporal sound output.
Figure 6:
NOTE: If zone 1 output of module is connected to strobes or
horn/strobes, or chime/strobes zone 1 input supply power
must be continuous for proper operation.
FACP
(+)
NAC1
(–)
(+)
NAC2
(–)
(+)
(–)
A0263-00
3
ANY SPECTRALERT
SPECTRALERT
HORN STROBE
HORN ONLY
HORN
POWER
}
TO NEXT
STROBE
DEVICE
POWER
OR EOL
CAUTION
HORN
ZONE 1
)
( +
CONTROL
OUT
)
( –
MA12/24D
OR PA400
HORN
ONLY
ZONE 1
ZONE 2
)
( +
IN
OUT
)
( –
ZONE 2
SYNC
)
( +
IN
ERROR
)
( –
MA12/24D
OR PA400
HORN
ONLY
SLAVE
SLAVE
)
( +
IN
OUT
)
( –
Horns will be Temporal
coded and in sync.
TEMP. JUMPER ON
}
TO NEXT
HORN POWER
OR EOL
A0265-00
TO NEXT
DEVICE OR
EOL
TO NEXT
DEVICE OR
EOL
A0186-00