1) The cable connecting sequence is not related with the station No.
2) Be sure to connect "terminal resistor" of the unit accessory to the units on both ends CC-Link
system. Connect the terminal resistor between "DA" and "DB".
3) In CC-Link system, the terminal resistor is different depending on the applied cable.
" CC-Link dedicated cable : 110Ω 1/2W (brown, brown, brown)
" CC-Link dedicated high-performance cable : 130Ω 1/2W (brown, orange, brown)
4) The master module can be connected to a place other than both ends.
5) A star connection cannot be used.
6) The connection method is shown below.
Terminal
resistor
IMPORTANT
The CC-Link dedicated cable and CC-Link dedicated high-performance cable cannot be used
together. If used together, correct data transmission will not be guaranteed.
POINT
Connect the shielded wire of the CC-Link dedicated cable to "SLD" of each module, and ground
both ends of the shielded wire using D type grounding via "FG".
The SLD and FG are connected into the module.