1) The cable connecting sequence is not related with the station No.
2) Be sure to connect "terminal resistor" of the unit accessory to the units on both ends CC-Link
system. Connect the terminal resistor between "DA" and "DB".
3) In CC-Link system, the terminal resistor is different depending on the applied cable.
" CC-Link dedicated cable : 110Ω 1/2W (brown, brown, brown)
" CC-Link dedicated high-performance cable : 130Ω 1/2W (brown, orange, brown)
4) The master module can be connected to a place other than both ends.
5) A star connection cannot be used.
6) The connection method is shown below.
Terminal
resistor
IMPORTANT
The CC-Link dedicated cable and CC-Link dedicated high-performance cable cannot be used
together. If used together, correct data transmission will not be guaranteed.
POINT
Connect the shielded wire of the CC-Link dedicated cable to "SLD" of each module, and ground
both ends of the shielded wire using D type grounding via "FG".
The SLD and FG are connected into the module.

6. Outline dimensions

Downloaded from
ManualsNet.com
Master module
DA
DB
DG
SLD
CC-Link
FG
dedicated cable
90(3.54)
search engine
Remote module
DA
DB
DG
SLD
CC-Link
FG
dedicated cable
Local module
DA
Terminal
DB
resistor
DG
SLD
FG
QJ61BT11
RUN
L RUN
MST
S MST
SD
RD
ERR.
L ERR.
STATION NO.
X10
X1
C
MODE
NC
1
NC
2
DA
3
SLD
4
DB
5
(FG)
6
DG
7
27.4(1.08)
Unit: mm(inch)

Advertisement

loading

This manual is also suitable for:

Qj61bt11-u-h-je