Controller Checks; Afdg/Afdu Checks; Safety Precautions - Trane AFDG Installation, Operation And Maintenance Manual

Air-cooled adaptive frequency drive with tracer® adaptiview control
Table of Contents

Advertisement

General Information
3. Use an ohmmeter to check for any short circuits
between the motor frame and the motor power leads.
If a short circuit exists, it must be corrected before
proceeding.

Controller Checks

4. Check that local, state and national electric codes have
been observed for the installation and wiring of this
equipment.
5. Check that all external power wiring has been properly
routed through the cabinet.
6. Check all input power and output power connections
for tightness.
7. Check the chassis ground and other connections for
tightness.
8. Check all external control connections (this includes
the operator station connections) for tightness.
9. Check to assure incoming power to the drive is phased
A, B, C.

AFDG/AFDU Checks

NOTICE
Perform Visual Inspection!
Before powering up this drive for the first time conduct
a visual inspection for the following:
Shipping damage.
Signs of moisture.
Signs of debris or dust from storage.
Signs of corrosion on components and/or enclosure.
These conditions could cause equipment damage. Do
not power up equipment if you have concerns
regarding equipment condition. Upon initial power up,
remain in the area for the first two hours of operation
and observe the chiller and drive for any abnormalities.
Contact CenTraVac™ Technical Support for assistance if
needed.
WARNING
Hazardous Voltage!
Failure to ensure that all enclosure doors are closed and
properly secured with fasteners when operating
equipment could result in death or serious injury.

Safety Precautions

1. This equipment should be adjusted and serviced by
qualified electrical maintenance personnel familiar
with the construction and operation of the equipment
and the hazards involved.
6
2. Be sure the input disconnect is in the correct position,
either "on" or "off" depending on the work to be
performed.
3. Check the status of the drive shutdown interlocks, if
used. These interlocks can be limit switches, guards or
safety switches installed around the driven machine or
the system interface controller.
WARNING
Bypassed Electrical Interlocks!
Failure to return all interlocks to operation when the
startup is completed could result in death, serious
injury or equipment damage. The electrical interlocks
provide machine and personal protection. If deactivated
or bypassed for servicing, use extreme caution when
performing the startup.
4. Check to see that the AFDG/AFDU is properly ground to
earth. See
"Grounding the Cabinet," p. 20
Power and Control Wiring," p.
WARNING
Proper Field Wiring and Grounding
Required!
Failure to follow code could result in death or serious
injury. All field wiring MUST be performed by qualified
personnel. Improperly installed and grounded field
wiring poses FIRE and ELECTROCUTION hazards. To
avoid these hazards, you MUST follow requirements for
field wiring installation and grounding as described in
NEC and your local/state electrical codes.
WARNING
Hazardous Voltage!
Failure to follow instructions below could result in
death, serious injury or equipment damage. Do NOT
remove or insert control boards or fuses while input
power is connected to the controller.
in
"Input
19.
AFDG-SVU01L-EN