Download Print this page

OCEANAIRE 2OACH1211 Engineering, Installation And Service Manual page 4

1-ton portable air-cooled heat pump1-ton portable air-cooled heat pump

Advertisement

SPECIFICATIONS
COOLING CAPACITY
HEATING CAPACITY
VOLTAGE
AMPS
TOTAL WATTS
IN RUSH AMPS
PLUG TYPE
EER
COMPRESSOR
COMPRESSOR HP
COMPRESSOR LRA
EVAP CFM - HIGH
EVAP MOTOR HP
COND CFM
COND MOTOR HP
CONDENSATE TANK
(Pump Optional)
REFRIGERANT CHARGE
HEIGHT
WIDTH
DEPTH
NET WEIGHT
SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE
Cooling Capacity
at high fan speed
Heating Capacity
Outdoor
Dedicated Circuit and Time Delay fuses/circuit breakers are recommended
EER is determined at high fan speed, with condenser discharge air ducted
into another area
CFM with free discharge
Amps & Watts at 115 Volts
COOLING AMBIENT
HEATING AMBIENT
NOT APPROVED FOR OUTDOOR
11,800 BTUH
11,000 BTUH
115V, 60Hz, 1PH
10.4
1180
60
5-15P, LCDI
10.0
ROTARY
1
50
400
1/8
580
1/8
5 GALLON
18 oz R-410A
38.7"
20.0"
26.7"
180 lb.
is total BTUH at 80ºDB/67ºWB return air, 95ºF Outdoor
is total BTUH at 70ºDB/60ºWB indoor, 47ºDB/43ºWB
OPERATING RANGE 65º TO 105º
OPERATING RANGE 40º TO 85º
2OACH1211