Vertical stacked water source heat pumps
Hide thumbs Also See for VSHP Series:
Table of Contents

Advertisement

OMEGA-VSHP.G-IOM-2205
Optionally Seal RA Perimeter w/
Foil Tape or Duct Board
Front of Cabinet to Drywall:
Min. 3"
Perimeter
RA Panel Frame
Optionally Seal RA Perimeter w/
Foil Tape or Duct Board
Front of Cabinet to Drywall:
Min. 4"
Perimeter Panel Furring Detail—Typ. 2x2 Framing Plan View
Notes:
1)Provide gap of 3" from framing finished drywall to cabinet. With optional 2-inch MERV 13 filter provide 4" from finished drywall to
cabinet. With optional flange, provide gap min. 1/4" from RA Panel to flange.
2) Return air panel should be centered in front of the unit return air opening.
3) With rear/side risers, allow for min. 6" typical clearance at the rear/side of the units.
4) For additional sound attenuation insulate the closet cavity with plenum rated acoustical insulation.
PLAN VIEW
VSHP CABINET &
PERIMETER RETURN AIR PANEL
VSHP/VSHY CABINET
Filter / Opt. Flange
to RA Panel
(Min. = 1/4")
2"
Rough-In Width
Filter / Opt. Flange
to RA Panel
(Min. = 1/4")
Unit Cabinet to Back Wall:
No Risers = Min. 1/2"
W/ Risers = Min. 6" Typ.
Standard 1" Filter
Screws x 6
Optional 2"
MERV 13 Filter
Unit Cabinet to Left/Right Wall:
W/ Nom. 2"x2" Studs = Min. 3"
Nom. 2x2 Studs Shown
(1-1/2" x 1-1/2")
Typ. 1/2" Drywall
31