OMEGA | WATER SOURCE HEAT PUMPS
Units comes with standard "Knockout" style discharge openings on top and all sides for field configuration.
This allows for custom discharge configurations based on site requirements. Discharge opening sizes are con-
figurable to meet site design conditions.
Supply Air Opening Sizes
Model
020
Horizontal
14 x 8
Top
12 x 12
Notes:
Discharge opening sizes are customer configurable. Published sizes shown are maximum factory default sizes.
Customer to verify discharge opening sizes match design requirements for proper airflow and select appropriate
discharge openings at time of order.
Unit comes standard with field "knockout" style discharge openings on all sides. Discharge flanges are 1-1/2
inches.
Line of Site Baffles (LOSB) are available where two or more horizontal discharge (Front, Left, Right and/or Back)
openings are specified.
All handing's determined by facing return air opening
Top Discharge is centered left and right, and offset 2 inches from the back.
22
VSHP Supply Discharge Opening (W X H) inches
030
040
050
14 x 8
14 x 10
16 x 12
12 x 12
12 x 12
14 x 12
060
080
100
16 x 12
18 x 14
18 x 16
14 x 12
14 x 14
16 x 14
OMEGA-VSHP.G-IOM-2205
120
18 x 16
16 x 16

Advertisement