CHILLER CONTROL MODEL 200 INSTALLATION AND OPERATION MANUAL Part No. 9843143 Effective June 22, 2000 Revised April 8, 2002 ® R E F R I G E R ATION PRODUCTS...
Description of the Equipment The Mueller Model 200 chiller control is designed to control chilled water temperature. The chiller control will accommodate 208/60/3, 230/60/3, or 460/60/3 electrical input. Outputs to control chiller water temperature are 24 volt to operate up to four stages of refrigeration.
Do not operate the pump dry.) Inspect and tighten all factory and field wiring connections before applying power. Chiller Control Model 200 Installation and Operation Manual Effective June 22, 2000 Part No. 9843143...
Connect condensing unit number three to the control circuit S3, terminal numbers 2 and 8. d. Connect condensing unit number four to the control circuit S4, terminal numbers 2 and 9. Chiller Control Model 200 Installation and Operation Manual Effective June 22, 2000 Part No.
Remove the jumper between terminals 4 and 5 in the electrical enclosure and wire the flow switch in series between terminals 4 and 5. Chiller Control Model 200 Installation and Operation Manual Effective June 22, 2000 Part No. 9843143...
Sensor < Low Alarm Alarm message displayed output ON or OFF according to setpoint Program Failure All outputs OFF Figure 1 - Temperature Control Chiller Control Model 200 Installation and Operation Manual Effective June 22, 2000 Part No. 9843143 Revised April 8, 2002...
Direct Cool “4d” Mandatory setting for “LS” chiller Reverse Heat “4r” Dead Band “4b” Not used for this application. Independent SP “4i” Chiller Control Model 200 Installation and Operation Manual Effective June 22, 2000 Part No. 9843143 Revised April 8, 2002...
Compressors should not cycle more than 5 times in a one-hour period. Figure 2 - Direct (Cool) Mode Schematic Chiller Control Model 200 Installation and Operation Manual Effective June 22, 2000 Part No. 9843143...
Repeat steps (b) through (e) for access and programming of the remaining parameters shown in Section 3.10. After all changes have been entered allow the control to sit idle until the current temperature is displayed. Chiller Control Model 200 Installation and Operation Manual Effective June 22, 2000 Part No. 9843143...
If the known product temperature does not correspond with the temperature display, the temperature control will require an operating parameter correction. This procedure is described in Sections 3.8 and 3.9, and is adjusted using the “So” code. Chiller Control Model 200 Installation and Operation Manual Effective June 22, 2000 Part No. 9843143...
SECTION 4.0 – DIAGRAMS Wiring Diagram, Part No. 9843161 Chiller Control Model 200 Installation and Operation Manual Effective June 22, 2000 Part No. 9843143 Revised April 8, 2002...
Wiring Diagram, Model 200 Control Box, Part No. 9001878 (Attached) Chiller Control Model 200 Installation and Operation Manual Effective June 22, 2000 Part No. 9843143 Revised April 8, 2002...
Paul Mueller Company (hereafter referred to as Company) will repair or (at the Company’s option) replace any part or portion of a Mueller Chiller Control found to be defective in workmanship or material under normal use, service, and installation procedures, for a period of one (1) year from date of installation by the original purchaser-user, or eighteen (18) months from the date of shipment from the Company factory, whichever occurs first.
SECTION 7.0 - INSTALLATION AND SERVICE NOTES Customer Name: Dealer Name: Address: Address: Telephone: Telephone: Chiller Control Model: Serial No.: Date of Installation: Notes: Chiller Control Model 200 Installation and Operation Manual Effective June 22, 2000 Part No. 9843143 Revised April 8, 2002...