3.6
Firing rate
The maximum output is chosen within area of the Fig. 2.
The minimum output must not be lower than the minimum limit of
the diagrams.
RS 28/M = 198 MBtu/hr 58 kW
RS 38/M = 266 MBtu/hr 78 kW
RS 50/M = 321 MBtu/hr 94 kW
NOTE:
The FIRING RATE areas given in figure (A) have been reduced
by 10% with respect to the maximum range that can be
reached. See "Procedure to refer burner operating condition
at an altitude and/or at a combustion supporter air tempera-
ture different to the standard values (328 ft above sea level, 68
°F)." on page 9 for operation at different ambient temperatures
and/or altitudes.
The firing rate was obtained considering a room
temperature of 68 °F and an atmospheric pressure
of 394 "WC (approx. 0 ft above sea level), with the
combustion head adjusted.