Table of contents SAFET Y AND PRECAUTIONS PRODUCT DESCRIPTION STOCK REF NUMBERS INTENDED AREA OF USE TECHNICAL DATA STANDARDS OPERATIONAL DIAGRAMS WIRING AND CONNECTIONS MOUNTING INSTRUCTIONS IN STEPS OPERATING INSTRUCTIONS ...
SAFET Y AND PRECAUTIONS Read all the information, the datasheet, mounting and operating instructions and study the wiring and connection diagram before working with the product. For personal and equipment safety, and for optimum product performance, make sure you entirely understand the contents before installing, using, or maintaining this product.
AC motors by varying the motor voltage through phase angle control. The integrated AC switch enables or disables the motor. STOCK REF NUMBERS Output regulation from low to high Stock Ref Nos Current Range (A) SC5001 1-1,5 SC5030 0,2-3 INTENDED AREA OF USE ■...
OPERATIONAL DIAGRAM From low to high speed Uout [%] 70 % 20 % Potentiometer position Of f Switch WIRING AND CONNECTIONS Power supply, line (230 VAC ±10 % / 50—60 Hz) Unregulated output, line (230 VAC ±10 % / 50—60 Hz, Imax 2 A) Power supply, neutral Unregulated output, neutral...
Page 6
Fig.1 Wiring and Connections Minimum speed Adjustment trimmer (factory pre set to 100 VAC) Power Supply Regulated output 230 VAC / 50—60 HZ motor 230VAC / 50‐60Hz to motor ...
Page 7
Surface mounting Disconnect the mains supply. Remove the knob by pulling it out. Unscrew the washer to remove the cover of the external enclosure. Mount the external enclosure onto the surface by means of the screws and dowels adhering to the mounting dimensions shown in Fig.
OPERATING INSTRUCTIONS Use only tools and equipment with non-conducting handles when working on electrical devices. The controller is to be used only with voltage controllable fans / motors. You can connect several motors to the controller as long as the current limit is not exceeded. The motor should be protected against overheating.