Page 1
english Speed controller For variable voltage 1~ fans Installation and Wiring Instructions Software version: D1349A from Version 1.00 L-BAL-E097-GB 1002 Index 001 Part.-No. 00163342-GB...
Installation and Wiring Instructions Speed controller General notes 1 General notes Structure of the operating instructions Before installation and start-up, read this manual carefully to ensure correct use! We emphasize that these operating instructions apply to specic units only, and are in no way valid for the complete system! Use these operating instructions to work safely with and on the device.
Installation and Wiring Instructions Speed controller Safety information Danger owing to electric current Danger owing to electric current or voltage. Information Important information and advice for user. Product safety The device conforms to the state of the art at the time of delivery and is fundamentally considered to be reliable.
Installation and Wiring Instructions Speed controller Product overview Attention! Automatically restart after a power failure or mains disconnection! Modications / interventions in the device Attention! For reasons of safety, no unauthorized interventions or modications may be made on the device. All planned modications must be authorized by the manufacturer in writing.
Installation and Wiring Instructions Speed controller Mounting Waste disposal / recycling Disposal must be carried out professionally and environmentally friendly in accordance with the legal stipulations. 4 Mounting General notes Attention! The following points must be complied with during the mechanical installation to avoid causing a defect in the device due to assembly errors or environmental inuences: •...
Installation and Wiring Instructions Speed controller Electrical installation Installation location for agriculture In order to avoid damage caused by ammoniac vapours, the controller shall not be installed in the stable, but rather in an outhouse wherever possible. Temperature inuences during commissioning Avoid condensation in the controller and hence functional faults attributable to condensation by storing the controller at room temperature! 5 Electrical installation...
Installation and Wiring Instructions Speed controller Electrical installation Motor connection The motor is connected at terminals U1 and U2. Several motors can be connected to the device. Attention The maximum total control current (specied for electronic voltage regulation) for all motors may not exceed the device’s rated current.
Installation and Wiring Instructions Speed controller Electrical installation Signal connection for setting the ouput voltage The unit has one-analog input: terminals “E1” / “GND” (Analog In 1). At this input the potentiometer mounted in the cover for setting the output voltage is connected (potentiometer outside).
Installation and Wiring Instructions Speed controller Electrical installation Enable, device ON / OFF (Digital In 1 = D1) Electronic disconnection and Reset after motor fault via oating contact at terminals “D1” - “D1” • Device “ON” for closed contact. • Controller “OFF”...
Installation and Wiring Instructions Speed controller Operating and display elements 6 Operating and display elements Potentiometer outside (0 - 100 %) Internal possibilities for settings and status LED °C n-max 20.03.2008 Pband n-min v_pxet_bedien_anzeige.VSD Potentiometer For control by potentiometer outside or by external signal without function (factory setting). Potentiometer without function Pband...
Installation and Wiring Instructions Speed controller Base setup 7 Base setup Function of dipswitches for operation as Speed controller (DIP For operation as a speed controller, the output voltage is set manually by adjusting the built-in potentiometer, by an external potentiometer or external signal. The desired function is determined with dipswitch S1.
Installation and Wiring Instructions Speed controller Start-up Start-up Prerequisites for commissioning Attention! 1. You must mount and connect the device in accordance with the operating instructions. 2. Check all connections for correctness once more. 3. The mains voltage must match the information on the rating plate. 4.
Installation and Wiring Instructions Speed controller Setting for operation Diagram: setting signal and speed 100 % Min. 0 % Max. = 100 % Min. 35 % Max. = 85 % 50 % Min. 0 – 10 V 10 – 0 V 0 –...
Installation and Wiring Instructions Speed controller Diagnostics / Faults 10 Diagnostics / Faults Operating conditions are indicated by the internal status LED with ashing code. Code Relay Reaction of Controller Explanation Adjustment In the event of a mains interruption the unit switches “OFF”...
Weight Type Part.-No. [Part.-No.] [kg] P-ET20 REF: 103 14 120 30 A 10 x 38 mm gRL (303629-30) (single fuse 00155984) {1} with supply voltage of 230 V / 50 Hz, values for other specications available on request line fuse {2} Max.
Installation and Wiring Instructions Speed controller Enclosure 11.2 Connection diagram F1=FF30 A P-ET20 Kontaktbelastung Contact rating max. AC 250 V 5 A A1 GND E1 GND Netz Line 1 ~ 120...277 V 50/60 Hz Eingang Input PEUN19K0 0...10 V 1 ~ Motor 14.01.2010 mit eingebauten Thermostatschaltern v_p-et20sd.VSD...
Page 19
Tel: 0844 8560590 Fax: 01293 565169 TECHNICAL SUPPORT: Tel: 0844 8560594 Fax: 01293 539209 Web:-www.vent-axia.com Email:- info@vent-axia.com As part of the policy of continuous product improvement Vent-Axia reserves the right to alter specications without notice. 443463A 1109 L-BAL-E097-GB 1002 Index 001 Part.-No. 00163342-GB 18/18...