3-2-2 Setting parameters

(1) Analog input unit (Target type: NA0AX06-MR, NA0AW06-MR)
Parameter
Resolution
Moving average execution times
<How to set parameters>
1) Right-click the analog unit registered in the system definition screen and left-click [Properties]. The "Module properties" dialog
box opens.
2) Click the [Parameter] button to display the "Analog Input Unit parameter setting" dialog box.
Set the resolution (data format) and moving average for each channel, and then click the [OK] button.
Setting range
14 bits or 16 bits
1 (No moving average) to 16 times
3-3