7.14 Function test of alarm system

Please follow below procedure in order to complete a function test of the applicable alarms on the
alarm system installed, either for frequency driven pumps (FCP), or a conventional driven pumps (PU).
Note there are 5 sec delay in the alarm system and if any alarm is present in the alarm system the auto
start/stop will not work, so please acc. all alarms on the alarm panel before you test the next alarm.
Overload alarm:
FCP systems: Indicate an overload of the current limit converter, class requirement is 200% for 1
minute; we do not recommend to test this. Disconnect the overload contact in motor controller or on
the frequency converter. See drawing for reference. The stand-by pump should start if not already
running.
PU systems: Push the test button on the overload relay in motor controller. The stand-by pump should
start if not already running.
Phase failure alarm:
Remove one of the fuses supplying the phase failure monitoring relay in the motor controller cabinet,
the stand-by pump should start if not already running.
Pw/Frequency failure:
Turn of main switch S1 in the motor controller or the circuit breaker from switch board. The stand-by
pump should start if not already running.
Power control failure alarm:
Set the S2 selector switch located on the outside of the motor controller cabinet to local control or
stop, the stand-by pump should start if not already running.
Low oil level alarm:
Disconnect the connection plug on top of the expansion tank.
The stand-by pump should start if not already running.
Hydraulic lock
alarm:
FCP systems: Disconnect X1- 2 in the connection boxes on top of the valve, there are one alarm box for
each pump.
PU systems: Activate manual solenoid in either direction while the motor controller is in remote
control. Keep activated for more than 5 seconds.
The stand-by pump should start if not already running.
High oil temp:
Remove the plug on the temperature sensor. This alarm do not have auto start of the stand-by pump.
KONGSBERG PROPRIETARY. This document and its accompanying elements contain KONGSBERG
information which is proprietary and confidential. Any disclosure, copying, distribution or use is prohibited if not
otherwise explicitly agreed with KONGSBERG in writing. Any authorized reproduction, in whole or in part, must
include this legend. ©2020 KONGSBERG - All rights reserved.