Page 1
DLC-02 Installation Manual DALI Controller...
Page 2
DLC-02 is a DALI-2 application controller to obtain the information of the DALI-2 system from DALI input device and control the DALI ECGs to make a lighting effect. Devices in the DALI bus can be scan, configure and set through the PC software. It also provides Modbus TCP communication protocol for the user to integrate the system, which is a simple way to install a DALI lighting system.
Page 3
Index 1.Safety Guidelines 4 5 . Application Example "Scene" example 4. . 5 1 2.Overview "Sequence" example 4. . 5 2 2.1 Overview Device "Color Cycle" example 2.2 Features 5.Modbus TCP Interface 2.3 Displays and Operating 5.1 Communication Timing Elements 5.2 Modbus protocol packet 2.4 Status LEDs architecture...
Page 4
■ μ μ μ μ Please do not install the unit in places with high moisture, high ambient POWER DLC-02 temperature or under direct sunlight. DALI Controller MOVE K L M 2 Overview DALI-A DALI-B ETHERNET 2 1 .
μ μ μ μ POWER Step 1: After connecting the computer and DLC-02 with a USB cable, open DLC-02 DALI Controller the DLC software and click "Connect" to ensure the normal MOVE communication between the computer and DLC-02.
Page 6
Step 2:Select "Scan" -> "New Initialization" on the DLC software and click 3 2 . Mounting "Start", the DLC software will assign randomly DALI short addresses to all devices on the bus and read back their parameters; Mount as shown in figure only, with DALI terminals down or else ●...
Page 7
DALI bus terminals Type L,N,K1,K2,K3,K4 DALI-A,DALI-B μ μ μ μ POWER 0.5 ~ 4.0mm 0.5 ~ 4.0mm Solid wire DLC-02 DALI Controller MOVE DALI-A DALI-B ETHERNET 0.5 ~ 2.5mm² 0.5 ~ 2.5mm² Stranded wire American wire 12 ~ 26AWG 12 ~ 26AWG...
Page 8
. . Modbus TCP communication DLC-02 supports Modbus TCP communication protocol. Using this communication function can control and monitor all devices on the DLC-02 bus. Refer to Chapter 5 for details. Note: Modbus TCP communication does not support DALI addressing and effect setting.
Page 9
※"Device Parameter": Only download device parameters to the lamps and input devices, the effects of DLC-02 remain unchanged. ※" Effect ": Only download effects to the DLC-02, the device parameters of the lamps and input devices remain unchanged. ※"Device Parameter and Effect": Download both device parameters...
Page 10
●Scan Assign addresses to devices connected to the DALI bus, and read back device parameters of the lamps and input devices. You can choose "New Installation" or "System Extension", as shown below: ※"Initial Installation": All devices on the DALI bus are re-addressed, but the previous parameters of devices remain unchanged.
Page 11
②Use " System Extension": After scanning, three lamps appear on bus A: the address of the colour temperature control type lamp is still A0, and the fade rate remains 358Steps/s; the address of the no colour control type lamp is still A1, and the fade time remains 90.5s; and the RGBW control type lamp is assigned the address of A2.
Page 12
●Lamp test You can turn on, blink or turn off the lamps, as shown below. ※ Bus A/B selection: When a bus is selected, the icon is displayed in red. ※Turn on/off all lamps on this bus. ※You can click the corresponding lamp icon to turn on, blink or turn off the lamp.
Page 13
●Firmware upgrade After opening the upgrade file, a new window will pop up showing the file name, device and firmware version. Click "Start" to upgrade the firmware. During the upgrade process, the DLC-02 will enter a reboot state. ●Generate Report Export the parameters of lamps and input devices as well as the “...
Page 14
4 1 4 . . About ●IP Setting You can set the IP address of the DLC-02. After entering the IP Display information about equipment model and software version. address, click "Write" and the IP address will be displayed on the DLC-02 screen.
Page 15
●change address: ※Use the "modify" button to change the current address to another unused address on the bus. ※Use the "exchange" button to swap the current address with other used addresses on the bus. Note: ※ the address modification function will take effect only when there are less than 64 devices on the bus (A or B)。...
Page 16
●If the device is colour TC type, click Enter the colour temperature configuration interface, you can set the colour temperature single step increment, physical warmest / coldest color temperature value, and customized warmest / coldest color temperature value of the lamp. 4 3 1 2 .
Page 17
4.3.1.2.3 Lamp test Parameter Value Comment Comment Lamp test includes: dimming test, color test (except DT6 If the color type of the device is "xy coordinate", the color adjustment test can be performed equipment) and scene test. Colour test ●x: ~0.8 ●There are two input methods ●y:...
Page 18
Note: When the AC is powered on for the first time, because the power-on time of the DLC-02 is not synchronized with the power-on response time of the DALI driver, if the bus fault detection of the DALI...
Page 19
4 3 2 . . Group Parameter Value Comment The group interface shows the grouping information of lamps on color control ● ●This option is only available when the bus. You can modify the grouping of lamps again and perform "Failure behavior"...
Page 20
4.3.3 Input devices Displays all DALI input devices connected to the bus (such as switch panels, occupancy sensors, light sensors, etc.). Right-click an input device to rename and change its address. 4.3.3.1 Renaming and modifying address ● Rename: You can modify the name in the green area below, and the character length is up to 12 characters.
Page 21
In this case, you can use the " Test: used to find Instance number " Parameter Value Comment and click " Start ". Test: used to ● Help users find target events. See Start find instance Section 4.3.3.3 for details number ●check:...
Page 22
4.3.3.4 Input device parameter setting description Parameter Value Comment PC software also provides input device parameter setting function, Button stuck/ ●check Enable or disable "Button stuck/ Click on the" " ,The parameter setting screen is displayed. Setting free event ●uncheck free event "...
Page 23
●Absolute sensor ●Presence/movement sensor The following table shows a description of the relevant parameters: Parameter Value Comment Position event ●check Enable or disable "Position reporting ●uncheck enabled event". Note: Only when "check" is selected, The following table shows a description of the relevant parameters: the "Slider"...
Page 24
4.3.4 Relay ●Light sensor In the relay interface, you can control the relay on/off action online The following table shows a description of the relevant parameters: Parameter Value Comment Luminance ●check Enable or disable "Luminance level The following table shows a description of the relevant parameters: ●uncheck level event event"...
Page 25
4.3.6 Sequence In the sequence interface, you can set the brightness or color of a The built-in timer function of DLC-02 allows you to set single lamp or group at different times. corresponding action events according to different time. For Click the "Add Sequence"...
Page 26
4 4 . Effect ●Effects are the core function of DLC-02, used to edit the logical ●Normal Dimming Lamp type Select the color type of the control relationship between the control device and the controlled device as well ●Colour object, and select it according to as the timing Settings.
Page 27
4. . 4 2 Effect Description 4 4.2.2 Output device window: The current available output devices are displayed. Specific output 4 4.2.1 Input event window: devices can be displayed via the drop-down menu. In the DALI Displays currently available input events. A specific input event can system, they act as controlled devices.
Page 28
4 4 3 . . Input event :Button Parameter Value Comment Set Buttons to control lamps, relays and sequence events.When a ●Disable: Disable short push Button is selected, the following parameter appears: Lamp/Group: ● Disable function to control lamps. Short push ●...
Page 29
It is valid when "Short press" will be added. sensor selects ""Toggle xxx". "Enable", the color temperature. commands DLC-02 does not respond to ●Diming x ●warmer: Long push to warm up commands from the occupancy ● Diming y the color temperature.
Page 30
Parameter Value Comment Parameter Value Comment Lamp/Group: ● Disable ●Disable: Disable short push Lamp/Group: When the colour ● change red: Long push to Double push ● Long push function to control lamps. type of the lamp is increase or decrease the brightness ●...
Page 31
Parameter Value Comment Parameter Value Comment ●disable: Disable double push to ●disable: Disable short push to ● disable Sequence: ● disable Relay: Double push control sequence. control relay. ● Sequence start Short push ● relay on ●Sequence start: Double push to ●relay on: Short push to open the ●...
Page 32
"occupancy event" and "idle event". ※Motion sensor: Corresponding to the "Motion Event" of DALI Part 303, when the DLC-02 detects the motion event reported by the sensor, it will execute the specified action. Before using the motion sensor, "movement Event" and "No movement Event"...
Page 33
4 4.5 Input event:light sensor Parameter Value Comment Control the lamps to maintain the target brightness range set by ●YES Lamp/group: ●YES: Enable the function of the Light sensor to achieve constant brightness. Automatically ●NO automatically turning off lamps; When the Light Sensor event is selected, the following parameters turn off ●NO: Disable the function of will appear:...
Page 34
4 4.6 Input event:timer Parameter Value Comment Set the Timer to control lamps, relays, and sequence events. When Lamp/group: ●disable: Disable timed events to ●disable the timer event is selected, the following parameters will appear: Timer event control lamps. ●OFF action go to level (only ●OFF: After the timed event is...
Page 35
Parameter Value Comment ●disable: Disable timed events to Lamp/group: ●Scene 1 ~ scene 16 This option is only available when Sequence: ● disable scene "Time Event Action" is selected as time event control the sequence. ● Sequence start action ● Sequence start: After the timed "go to scene".
Page 36
The following table shows a description of the relevant parameters: 4 5 . Application Example Parameter Value Comment 4 5 1 . . “Scene” example ●Normal Dimming Colour mode Choose a color type. Taking hotel lighting as an example, there are four color temperature ●...
Page 37
Step 2: Group and scene settings ※Group setting Select one of the lamps LED 1, click "Bus Group Setting - Edit" to open the group editing interface, check "Group 1" to add LED 1 to the group, and click "Save" to complete the setting. Use the same method to add LED 2, LED 3 and LED 4 to group Step 3: Enable input events Use "Button 1", "Button 2"...
Page 38
Click the "Settings" button, check the "Enable button short press event", and set the "short press time" to 500ms, please refer to Chapter 4.3.3.4 "Button" for the relevant parameter description, and click "Confirm" to complete the setting. Use the same method and the same parameters to set Button 2 and Button 3.
Page 39
18:00 pm,turn off all lights. Implementation steps: Step 1:Add all lamps in the office to "group 1" of bus A, as shown below: Step 5: Finally, click "download" to download the device parameters and effect configuration to the input devices, lamps and DLC-02.
Page 40
"Sequence" interface. The lamp color mode parameter in the "Effect" interface is invalid for "sequence" Step 3:Create Sequence 1 and configure it as follows: Step 5: Finally, click " Download " to download the current device parameter and effect configuration to the input device, lamp and DLC-02.
Page 41
4 5 3 . . "Color Cycle" example Step 2:Enable input events Taking the exterior wall lighting application as an example, suppose a Use Button 1 in the switch panel as the input event and check enable to building has four floors, and 16 RGBW lamps are installed on the exterior start;...
Page 42
Step 3:Greate sequence Four new sequences are added and named as the first, second, third and fourth floor respectively, which are used to set the color change effect of lamps on each floor The color change configuration of lamps on each floor is as follows:...
Page 43
" to download the current device parameter and effect configuration to the input device, lamp and DLC-02 Click "+ Add" to create the effect, and set it as shown below: ※ Move the input event "Button 1", the sequence "...
Page 44
Word data must comply with the High Byte transmission principle. The external software (Client) can use this interface to control and MBAP Header Function Code Data monitor THE DLC-02(Server), including the minimum brightness level, 7bytes 1bytes N bytes maximum brightness level, system power-on behavior, dimming time and other DALI instructions.
Page 45
03 will ask the Server device to send back the parameter state value Read Address of Write of Write Register Address of of the sender. Here is the Function Code used by DLC-02. Read Registers Write Registers Register Value...
Page 46
DALI B bus, up to 128. ※40001-40006needs to be used with 30001-30004, and 42001-42002 needs to be used with 32001-32004. Please refer to the Data framework. ★You must use THE DLC-02 software to scan for input Device events.
Page 47
0: Unlock motion sensor control Lock/Unlock Motion Sensor 1: Lock motion sensor control Controls Note: This function can be triggered in DLC-02 PC softwareLock/Unlock motion set by Effectcontrol function, realize manual/automatic control switching. Set the current color type of the...
Page 48
Read data format 32001 to 32004 in control Gear registers: Name Description Byte Byte Name Description set color value Set the current color value, divided into the following two cases: serial number The command sequence number is the same as sent before ( ) 1 If the color type is colour temperature TC: Byte 4 Byte 5...
Page 49
Read registers 34002 to 34257 of DALI A's input device event information: Data format for control relay registers 43001 to 43004: Byte Name Description Name Description Byte Control relay 1 0: Relay off instance type instance type: 1: relay on 1: Push-button reserve 2: Slider...
Page 50
5 6 . Communication Examples Read DALI B bus input device event information registers 35002 to 35257 format: Examples of Modbus TCP control and DALI device query are provided Byte Name Description 5 6 1 . . Pass through DALI instructions Device address Single device address: 0-63 Query the minimum brightness value of DALI BUS A0 device,...
Page 51
. . Reading relay status 0x0004: Indicates that the number of registers to be written is 4, Query the status of the four relays of DLC-02. The status of response namely 41001 to 41004. 0x08: Byte Count, indicating 8 bytes of relay 1 is closed, and that of relays 2 to 4 is off.
Page 52
5 6 5 . . Reading Input Device Events recorded by DALI A 5 7 . Incorrect Response Instance 2 of sensor A1 is occupied and movement is detected. Error handling will occur when sending data that does not conform to the request:...
6 1 . Bus Info The menu is used to scan total quantity of input and output devices connected The display on the DLC-02 can parameterize maximum level, minimum level, to the controller. The example below shows there is one input device and one...
Page 54
6 2 3 Scene Test The operation instructions are shown as follows: Set a single lamp or all of the lamp s on the DALI A/B a specific scene. ● ①Config Lamp Addr Bus: 1 represents DALI-A, 2 represents DALI-B. ●...
Page 55
② When DHCP is selected, the DLC-02 will be assigned IP address automatically. It does not need to do any manual configuration to connect the controller to local devices or gain access to the Web.
Set Time effectively. Set IP Addr ※MEAN WELL possesses the right to adjust the content of this manual. Language English Please refer to the latest version of our manual on our website. Firm UER R1 1 https://www.meanwell.com...
Page 57
N o . 2 8 , W u q u a n 3 r d R d . , W u g u D i s t . , N e w Ta i p e i C i t y 2 4 8 , Ta i w a n...
Need help?
Do you have a question about the DLC-02 and is the answer not in the manual?