Refrigerant Connections; Indoor Unit Condensation Drain Connection - Lamborghini Caloreclima RUBINO PLUS 7 Use And Maintenance Manual

Monosplit dc inverter in heat pump
Table of Contents

Advertisement

Available languages

Available languages

RUBINO PLUS

2.6 REFRIGERANT CONNECTIONS

To connect the refrigerant lines, proceed as follows ("fig. 18 -"):
• Match the ends of the previously flared pipe with those of the connections on the indoor units
• Screw the union by hand and then tighten it with a suitable wrench (to avoid tension on the pipes it is advisable to also use a second
wrench).
fig. 18 -
Note: in combination with 18000 indoor units, use the pipe adapter kit "fig. 19 -" – "fig. 20 -".
These kits are provided with outdoor units and must be connected to the faucet on the outdoor unit. Complete the operation by con-
necting the ½" pipe needed to connect to the indoor unit.

2.7 INDOOR UNIT CONDENSATION DRAIN CONNECTION

Indoor units are provided as standard with the drain hose connection in position A ("fig. 21 -").If necessary, it is possible to move the
connection position to the opposite site.In order to do this, remove the plug from the initial position B ("fig. 21 -") and move it to position
A ("fig. 21 -").
While making the fittings ("fig. 22 -") for the condensation drain remember that:
• The diameter of the condensation drain hose must be equal to or higher than the one of the fitting pipe.
• Seal the joints and wrap them with insulating material to avoid the formation of condensation on the hose external surfaces.
• Keep the condensation drain hose short and with a downward inclination of at least 1/100.
• Do not bend the condensation drain hose.
• After connecting the hose, check that the condensation water can easily flow.
• To check drainage, pour water in the condensation drain tray ("fig. 23 -").
fig. 21 -
Cod. 3QE46190 - Rev. 01 - 10/2020
fig. 19 -
fig. 20 -
fig. 22 -
fig. 23 -