Modbus Register Map - Honeywell LeakFilm MC Technical Manual

Master controller with rs-485 modbus
Table of Contents

Advertisement

LeakFilm MC Technical Manual
MAN0966 04-15
Modbus
Description
Register
Address
30117
Status of slave controller (ID:001)
Leak location for LeakFilm Pro
(ID:001)
30118
Status for LeakFilm 5 (ID:001)
Not used for LeakFilm HC (ID:001)
30119
Reserved
~30132
30133
Status of slave controller (ID:002)
Leak location for LeakFilm Pro
(ID:002)
30134
Status for LeakFilm 5 (ID:002)
Not used for LeakFilm HC (ID:002)
30135 ~
Reserved
30148
......
......
30341
Status of slave controller (ID:015)
Leak location for LeakFilm Pro
(ID:015)
30342
Status for LeakFilm 5 (ID:015)
Not used for LeakFilm HC (ID:015)
30343 ~
Reserved
30356
30357
Status of slave controller (ID:016)

10. MODBUS Register Map

R/W
Size
Note
(Word)
Bit 0: 0-Normal, 1-Leak
Bit 2: 0-Normal, 1-Sensor Broken
R
1
Bit 8: 0-Normal, 1-Comm. Err
Bit 9: 0-Modbus not use, 1-Modbus use
For LeakFilm Pro
Bit 0 ~ Bit 15: Leak Location
Ex1) 0x00 0x78: 120 (dec) / 10 = 12.0m
Ex2) 0x04 0xF6: 1270 (dec) / 10 = 127.0m
For LeakFilm 5
Bit 0: 0-CH1 Normal, 1-CH1 Leak
Bit 1: 0-CH2 Normal, 1-CH2 Leak
R
1
Bit 2: 0-CH3 Normal, 1-CH3 Leak
Bit 3: 0-CH4 Normal, 1-CH4 Leak
Bit 4: 0-CH5 Normal, 1-CH5 Leak
Bit 5: 0-CH1 Normal, 1-CH1 Sensor Broken
Bit 6: 0-CH2 Normal, 1-CH2 Sensor Broken
Bit 7: 0-CH3 Normal, 1-CH3 Sensor Broken
Bit 8: 0-CH4 Normal, 1-CH4 Sensor Broken
Bit 9: 0-CH5 Normal, 1-CH5 Sensor Broken
N/A
14
Reserved for future expansion
R
1
Same as register 30117. See above note.
R
1
Same as register 30118. See above note.
N/A
14
Reserved for future expansion
...
...
......
R
1
Same as register 30117. See above note.
Same as register 30118. See above note.
R
1
* LeakFilm 5 can be connected only up to 15.
N/A
14
Reserved for future expansion
R
1
Same as register 30117. See above note.
22