LeakFilm MC Technical Manual
MAN0966 04-15
6. Electrical connections and power on
The communication ID of LeakFilm MC is set by SW3 dip switch. See in the below table how
to set the ID using the SW3 dip switch.
SW3
1
2
On Off Off Off Off Off Off Off ID = 1 (Default value)
On Off Off On Off Off Off Off ID = 1 + 2x0 + 4x0 + 8x1 = 9
Value
Off Off Off Off Off On Off Off
Table 3: Examples of communication ID setting of LeakFilm MC
User can set MaxMD using the SW4 dip switch as shown in the below table. If MaxMD is
7, LeakFilm MC scans from 1 to 7 only. In this case any controller with an ID of more than
7 will not be scanned, so it will not be monitored by the LeakFilm MC. To avoid missing any
controllers that are connected to the LeakFilm MC, leave MaxMD set to the default value
of 200.
SW4
1
2
On Off On Off On Off Off Off MaxMD = 1 + 4x1 + 16x1 = 21
Off Off Off Off Off On On Off MaxMD = 32x1 + 64x1 = 96
Value
Off Off Off On Off Off On On
3
4
5
6
7
3
4
5
6
7
Table 4: Examples of MaxMD setting of LeakFilm MC
8
ID = 0 + 2x0 + 4x0 + 8x0 + 16x0
+ 32x1 = 32 (Max. value)
8
MaxMD
MaxMD = 8x1 + 64x1 + 128x1
= 200 (Default value)
15
3013M5005 Issue 3
ID