TOPAX L1 / L4 / L5 For free chlorine, chlorine dioxide or hydrogen peroxide Operation & Maintenance Instructions Read these operation and maintenance instructions before start up! To be held for future reference. Dosing Liquids Conveying Gases Control Systems...
1.) Read and follow all instructions! .) WARNING! To reduce risk of injury, do not permit children to use this product unless they are closely supervised at all times. WARNING! 4 | Operation & Maintenance Instructions TOPAX L1/L4/L5 | General and Safety Instructions...
The procedure specified in this Operation & Maintenance Manual for shutting down the Dosing/pump/system must be observed without fail. Dosing pumps or systems in contact with potentially harmful media must be decontami- nated. General and Safety Instructions | Operation & Maintenance Instructions TOPAX L1/L4/L5 | 5...
Should the device need to be permanently taken out of operation, please bear in mind that it contains electrolytic capacitors and must therefore be disposed of accordingly. 6 | Operation & Maintenance Instructions TOPAX L1/L4/L5 | General and Safety Instructions...
ClO 1 Measurement input for Pt100 Digital input water deficiency safety Digitale Interfaces RS485, Baud rate 9600, dataformat 8Bit, (Optional) 1start and 1stop bit, no even parity General and Safety Instructions | Operation & Maintenance Instructions TOPAX L1/L4/L5 | 7...
Use a screwdriver to adjust the lock-on clip screws until the device is firmly in place. Device Installation and Connection | Operation & Maintenance Instructions TOPAX L1/L4/L5 | 11...
Either fit the terminal covering back on, or proceed directly with the various connections. 1 | Operation & Maintenance Instructions TOPAX L1/L4/L5 | Device Installation and Connection...
The “ESC” key will always bring you back to the measuring value indication. Instructions for Device Operatio | Operation & Maintenance Instructions TOPAX L1/L4/L5 | 17...
Save your settings by pressing the key. The double triangle will disappear. NOTE If you do not wish to save a setting, press the “ESC” key instead of the key. NOTE! 18 | Operation & Maintenance Instructions TOPAX L1/L4/L5 | Instructions for Device Operatio...
1) Basic settings: Password codes and languages 2) Metering unit settings: calibration, temperature compensation 3) Controller setting: Selection of controller variant and corresponding parameters 4) Data readout settings: analog, digital and/or as alarm Instructions for Device Operatio | Operation & Maintenance Instructions TOPAX L1/L4/L5 | 19...
Since the language settings are part of the fundamental device settings, password code 86 is necessary. If a different password code has been set, you will immediately be requested to enter the required code number. 0 | Operation & Maintenance Instructions TOPAX L1/L4/L5 | Password Codes and Languages...
DPD calibration with chlo- rinated water. NOTE! Details about optimum slope rate and the slope rate alarm limits are found in the “Error Advisory” chapter. NOTE! Metering Unit Settings | Operation & Maintenance Instructions TOPAX L1/L4/L5 | 1...
Page 22
“mg/l Cl” by a factor of 1.9 since photometric measuring only records the molecule count and chlorine dioxide molecules are heavier than chlorine molecules. | Operation & Maintenance Instructions TOPAX L1/L4/L5 | Metering Unit Settings...
The temperature measurement can thus be calibrated. Measure the temperature once manually while putting the device into operation and correct for the temperature measurement accordingly. Metering Unit Settings | Operation & Maintenance Instructions TOPAX L1/L4/L5 | 3...
The “I” gain locks on later than the P-Controller and princi- pally eliminates residual control deviation, which is always present with the P-Controller. 4 | Operation & Maintenance Instructions TOPAX L1/L4/L5 | Controller Unit Settings...
When the hysteresis is set, the relay does not switch until the set point has been exceeded or under-run by half of the hysteresis. Controller Unit Settings | Operation & Maintenance Instructions TOPAX L1/L4/L5 | 5...
4) Effective operating direction for S1 and S2 Set the “raise“ option, if metering increases the measurement value. Set the “lower” option if metering decreases the measurement value. 6 | Operation & Maintenance Instructions TOPAX L1/L4/L5 | Controller Unit Settings...
(pause) proportional to the control deviation. 6) Minimum pulse time: Set the minimum time that the relay must be CLOSED such that the connected actuator meters out any amount at all. Controller Unit Settings | Operation & Maintenance Instructions TOPAX L1/L4/L5 | 7...
“Water Deficiency” message will come up on display. NOTE! This function can also be utilised as a water deficiency protection by connecting a float gauge. NOTE! 8 | Operation & Maintenance Instructions TOPAX L1/L4/L5 | Controller Unit Settings...
In other words, the alarm will be activated only when the threshold value is either excee- ded or under-run for a longer period of time than the delay time setting. 30 | Operation & Maintenance Instructions TOPAX L1/L4/L5 | Controller Unit Settings...
− between register output and controller output If the controller is integrated into a data network, a bus address between 1 and 15 must be entered. CAUTION! The bus address “10” is not allowed. CAUTION! Data Readout | Operation & Maintenance Instructions TOPAX L1/L4/L5 | 31...
At both ends of the network the data line has to be cut off with a resistance of 120 ohm. It is possible to put the switch for the resistance on the last TOPAX L/LF in the network 3 | Operation & Maintenance Instructions TOPAX L1/L4/L5 | Data Readout...
Page 33
Standard and Mini. The programme “TopView 2.0 Standard” has the order no. 78349. The Software “TopView 2.0 Mini” is free to download from the manufacturer’s website. CAUTION! NOTE! Operation and Maintenance | Operation & Maintenance Instructions TOPAX L1/L4/L5 | 33...
During each calibration, the device tests the utility of the sensors and specifies when a sensor needs to be cleaned or replaced. For more details, please refer to the “Error Advisory” section of this manual. 34 | Operation & Maintenance Instructions TOPAX L1/L4/L5 | Service...
This process takes a few seconds. Once done, the device will return automatically to the initial measurement display page, and the controller operations will be switched off. Error advisory | Operation & Maintenance Instructions TOPAX L1/L4/L5 | 35...
Close the input when you wish to proceed closed. with control. When a water deficiency sensor is con- nected, this error advisory indicates that the measurement water supply has been interrupted. 36 | Operation & Maintenance Instructions TOPAX L1/L4/L5 | Error advisory...
This declaration is no assurance of characteristics in the sense of the product liability law. The safety notes in the operation & maintenance instructions must be observed. Page 1 of 2 40 | Operation & Maintenance Instructions TOPAX L1/L4/L5 | Index...
Page 41
Page 2 of 2 Declaration of conformity | Operation & Maintenance Instructions TOPAX L1/L4/L5 | 41...
It contains all the technical information required for installation, start-up and maintenance. Should you have any questions or require further information regarding these operating instructions, please contact the manufacturer or its official national representative. 4 | Operation & Maintenance Instructions TOPAX L1/L4/L5 | Revision...
Commissioning (date): ............................ Duty peroid (approx. operating hours): ......................Please describe the specifics of the installation and provide a simple diagram with details of the material, diameter, length and levels. Warranty Application | Operation & Maintenance Instructions TOPAX L1/L4/L5 | 43...