TOPAX L1 / L4 / L5
For free chlorine, chlorine dioxide or hydrogen peroxide
Operation &
EN
02
Maintenance Instructions
Read these operation and maintenance instructions
before start up!
To be held for future reference.
Dosing
Liquids
Conveying
Gases
Control
Systems

Advertisement

Table of Contents
loading

Summary of Contents for Jesco TOPAX L1

  • Page 1 TOPAX L1 / L4 / L5 For free chlorine, chlorine dioxide or hydrogen peroxide Operation & Maintenance Instructions Read these operation and maintenance instructions before start up! To be held for future reference. Dosing Liquids Conveying Gases Control Systems...
  • Page 2: Table Of Contents

    6. Controller Unit Settings ..................4 6.1 ON/OFF-Controller ..................25 6.2 P-/PI-Controller as pulse-frequency controller ..........26 6.3 P-/PI-Controller as pulse-pause controller ............27 6.4 Controller activation and deactivation ............. 28  | Operation & Maintenance Instructions TOPAX L1/L4/L5 | Table of Contents...
  • Page 3 9.3 Erase Settings (Reset) ................... 35 10. Error advisory ....................36 11. Index ......................... 37 1. Declaration of conformity ................40 13. Revision ......................4 14. Warranty Application ..................43 Table of Contents | Operation & Maintenance Instructions TOPAX L1/L4/L5 | 3...
  • Page 4: General And Safety Instructions

    1.) Read and follow all instructions! .) WARNING! To reduce risk of injury, do not permit children to use this product unless they are closely supervised at all times. WARNING! 4 | Operation & Maintenance Instructions TOPAX L1/L4/L5 | General and Safety Instructions...
  • Page 5: Hazards Due To Non-Compliance With Safety Instructions

    The procedure specified in this Operation & Maintenance Manual for shutting down the Dosing/pump/system must be observed without fail. Dosing pumps or systems in contact with potentially harmful media must be decontami- nated. General and Safety Instructions | Operation & Maintenance Instructions TOPAX L1/L4/L5 | 5...
  • Page 6: Unauthorized Modifications And Production Of Spare Parts

    Should the device need to be permanently taken out of operation, please bear in mind that it contains electrolytic capacitors and must therefore be disposed of accordingly. 6 | Operation & Maintenance Instructions TOPAX L1/L4/L5 | General and Safety Instructions...
  • Page 7: Overview Of Device Functions

    ClO 1 Measurement input for Pt100 Digital input water deficiency safety Digitale Interfaces RS485, Baud rate 9600, dataformat 8Bit, (Optional) 1start and 1stop bit, no even parity General and Safety Instructions | Operation & Maintenance Instructions TOPAX L1/L4/L5 | 7...
  • Page 8: Technical Data

    6 A/ 250 V, max. 550 VA ohmic resistive load (with RC protective circuit) Operating tempe- 0 – 50°C rature Storage temperature -20 – 65°C Atmospheric humidity 0 – 90% non-condensing 8 | Operation & Maintenance Instructions TOPAX L1/L4/L5 | General and Safety Instructions...
  • Page 9: Device Installation And Connection

    47 nF 260 V 22 Ohm 2 Watt 150 mA 100 nF 260 V 47 Ohm 2 Watt 1,0 A 220 nF 260 V 47 Ohm 2 Watt Device Installation and Connection | Operation & Maintenance Instructions TOPAX L1/L4/L5 | 9...
  • Page 10: Dimensions

    .1 Dimensions Built-in Casing Option: Front door Wall-mounted Casing 10 | Operation & Maintenance Instructions TOPAX L1/L4/L5 | Device Installation and Connection...
  • Page 11: Installation Of Built-In Casing

    Use a screwdriver to adjust the lock-on clip screws until the device is firmly in place. Device Installation and Connection | Operation & Maintenance Instructions TOPAX L1/L4/L5 | 11...
  • Page 12: Installation Of Wall-Mounted Casing

    Either fit the terminal covering back on, or proceed directly with the various connections. 1 | Operation & Maintenance Instructions TOPAX L1/L4/L5 | Device Installation and Connection...
  • Page 13: Terminal Connection Diagram Of Built-In Casing

    Bridge circuits = termination impedance activated Terminal connection of electrodes Potentiostatic electrode, Type PM-J, <4 mg/l Relay 1 Relay 2 Relay 3 RS 485 (OPTION) Device Installation and Connection | Operation & Maintenance Instructions TOPAX L1/L4/L5 | 13 Relay 1...
  • Page 14 Relay 2 Relay 3 RS 485 (OPTION) Relay 1 Relay 2 Relay 3 Hydrogen peroxide electrode RS 485 (OPTION) Relay 1 Relay 2 Relay 3 RS 485 (OPTION) 14 | Operation & Maintenance Instructions TOPAX L1/L4/L5 | Device Installation and Connection...
  • Page 15: Terminal Connection Diagram Of Built-In Casing

    Potentiostatic electrode, Type PM-J, <4 mg/l Relay 1 Relay 3 Relay 2 Power Supply RS 485 Jumper RS 485 Termination impedance water deficiency Device Installation and Connection | Operation & Maintenance Instructions TOPAX L1/L4/L5 | 15 Relay 1 Relay 3...
  • Page 16 Relay 1 Relay 3 Relay 2 Power Supply RS 485 Power Supply Jumper RS 485 Termination impedance RS 485 Jumper RS 485 Termination impedance water deficiency water deficiency 16 | Operation & Maintenance Instructions TOPAX L1/L4/L5 | Device Installation and Connection...
  • Page 17: Instructions For Device Operation

    The “ESC” key will always bring you back to the measuring value indication. Instructions for Device Operatio | Operation & Maintenance Instructions TOPAX L1/L4/L5 | 17...
  • Page 18: Parameter Settings

    Save your settings by pressing the  key. The double triangle will disappear. NOTE If you do not wish to save a setting, press the “ESC” key instead of the  key. NOTE! 18 | Operation & Maintenance Instructions TOPAX L1/L4/L5 | Instructions for Device Operatio...
  • Page 19: Menu Overview

    1) Basic settings: Password codes and languages 2) Metering unit settings: calibration, temperature compensation 3) Controller setting: Selection of controller variant and corresponding parameters 4) Data readout settings: analog, digital and/or as alarm Instructions for Device Operatio | Operation & Maintenance Instructions TOPAX L1/L4/L5 | 19...
  • Page 20: Password Codes And Languages

    Since the language settings are part of the fundamental device settings, password code 86 is necessary. If a different password code has been set, you will immediately be requested to enter the required code number. 0 | Operation & Maintenance Instructions TOPAX L1/L4/L5 | Password Codes and Languages...
  • Page 21: Metering Unit Settings

    DPD calibration with chlo- rinated water. NOTE! Details about optimum slope rate and the slope rate alarm limits are found in the “Error Advisory” chapter. NOTE! Metering Unit Settings | Operation & Maintenance Instructions TOPAX L1/L4/L5 | 1...
  • Page 22 “mg/l Cl” by a factor of 1.9 since photometric measuring only records the molecule count and chlorine dioxide molecules are heavier than chlorine molecules.  | Operation & Maintenance Instructions TOPAX L1/L4/L5 | Metering Unit Settings...
  • Page 23: Temperature Compensation

    The temperature measurement can thus be calibrated. Measure the temperature once manually while putting the device into operation and correct for the temperature measurement accordingly. Metering Unit Settings | Operation & Maintenance Instructions TOPAX L1/L4/L5 | 3...
  • Page 24: Controller Unit Settings

    The “I” gain locks on later than the P-Controller and princi- pally eliminates residual control deviation, which is always present with the P-Controller. 4 | Operation & Maintenance Instructions TOPAX L1/L4/L5 | Controller Unit Settings...
  • Page 25: On/Off-Controller

    When the hysteresis is set, the relay does not switch until the set point has been exceeded or under-run by half of the hysteresis. Controller Unit Settings | Operation & Maintenance Instructions TOPAX L1/L4/L5 | 5...
  • Page 26: P-/Pi-Controller As Pulse-Frequency Controller

    4) Effective operating direction for S1 and S2 Set the “raise“ option, if metering increases the measurement value. Set the “lower” option if metering decreases the measurement value. 6 | Operation & Maintenance Instructions TOPAX L1/L4/L5 | Controller Unit Settings...
  • Page 27: P-/Pi-Controller As Pulse-Pause Controller

    (pause) proportional to the control deviation. 6) Minimum pulse time: Set the minimum time that the relay must be CLOSED such that the connected actuator meters out any amount at all. Controller Unit Settings | Operation & Maintenance Instructions TOPAX L1/L4/L5 | 7...
  • Page 28: Controller Activation And Deactivation

    “Water Deficiency” message will come up on display. NOTE! This function can also be utilised as a water deficiency protection by connecting a float gauge. NOTE! 8 | Operation & Maintenance Instructions TOPAX L1/L4/L5 | Controller Unit Settings...
  • Page 29: Manual Relay Control

    With the  key, switch the controller to manual operation. Using the  key, change between manual operation <> S1 switch mode <> S2 switch mode <> manual operation. Controller Unit Settings | Operation & Maintenance Instructions TOPAX L1/L4/L5 | 9...
  • Page 30: Alarm

    In other words, the alarm will be activated only when the threshold value is either excee- ded or under-run for a longer period of time than the delay time setting. 30 | Operation & Maintenance Instructions TOPAX L1/L4/L5 | Controller Unit Settings...
  • Page 31: Data Readout

    − between register output and controller output If the controller is integrated into a data network, a bus address between 1 and 15 must be entered. CAUTION! The bus address “10” is not allowed. CAUTION! Data Readout | Operation & Maintenance Instructions TOPAX L1/L4/L5 | 31...
  • Page 32: Current Output

    At both ends of the network the data line has to be cut off with a resistance of 120 ohm. It is possible to put the switch for the resistance on the last TOPAX L/LF in the network 3 | Operation & Maintenance Instructions TOPAX L1/L4/L5 | Data Readout...
  • Page 33 Standard and Mini. The programme “TopView 2.0 Standard” has the order no. 78349. The Software “TopView 2.0 Mini” is free to download from the manufacturer’s website. CAUTION! NOTE! Operation and Maintenance | Operation & Maintenance Instructions TOPAX L1/L4/L5 | 33...
  • Page 34: Operation And Maintenance

    During each calibration, the device tests the utility of the sensors and specifies when a sensor needs to be cleaned or replaced. For more details, please refer to the “Error Advisory” section of this manual. 34 | Operation & Maintenance Instructions TOPAX L1/L4/L5 | Service...
  • Page 35: Service

    This process takes a few seconds. Once done, the device will return automatically to the initial measurement display page, and the controller operations will be switched off. Error advisory | Operation & Maintenance Instructions TOPAX L1/L4/L5 | 35...
  • Page 36: Error Advisory

    Close the input when you wish to proceed closed. with control. When a water deficiency sensor is con- nected, this error advisory indicates that the measurement water supply has been interrupted. 36 | Operation & Maintenance Instructions TOPAX L1/L4/L5 | Error advisory...
  • Page 37: Index

    Device data ......................35 Device functions ......................7 Dimensions ......................10 Display ........................17 Erase Settings ......................35 Error advisory ......................36 External controller stop .....................28 Hysteresis........................25 Installation built-in casing ..................11 Installation wall-mounted casing ................12 Interface ........................7 Error advisory | Operation & Maintenance Instructions TOPAX L1/L4/L5 | 37...
  • Page 38 Manual relay control ..................29 RC-protective circuit ....................9 Reset ........................35 RS485 ........................31 Sensors ........................14 Service ........................35 Set point........................24 Setting controller unit ....................24 Setting metering unit ....................21 Setting parameters....................18 Technical data ......................8 Temperature compensation ..................23 38 | Operation & Maintenance Instructions TOPAX L1/L4/L5 | Index...
  • Page 39 Built-in casing ....................13 wall-mounted casing ..................15 TopView ........................33 Warranty .........................43 Index | Operation & Maintenance Instructions TOPAX L1/L4/L5 | 39...
  • Page 40: Declaration Of Conformity

    This declaration is no assurance of characteristics in the sense of the product liability law. The safety notes in the operation & maintenance instructions must be observed. Page 1 of 2 40 | Operation & Maintenance Instructions TOPAX L1/L4/L5 | Index...
  • Page 41 Page 2 of 2 Declaration of conformity | Operation & Maintenance Instructions TOPAX L1/L4/L5 | 41...
  • Page 42: Revision

    It contains all the technical information required for installation, start-up and maintenance. Should you have any questions or require further information regarding these operating instructions, please contact the manufacturer or its official national representative. 4 | Operation & Maintenance Instructions TOPAX L1/L4/L5 | Revision...
  • Page 43: Warranty Application

    Commissioning (date): ............................ Duty peroid (approx. operating hours): ......................Please describe the specifics of the installation and provide a simple diagram with details of the material, diameter, length and levels. Warranty Application | Operation & Maintenance Instructions TOPAX L1/L4/L5 | 43...