Specification Of Main Unit - Kanomax 6332 Operation Manual

Air flow transducer
Hide thumbs Also See for 6332:
Table of Contents

Advertisement

Specification of Main Unit

Product Name
Model
Measuring Object
Output
Output Range
Display Resolution
(6332D)
Power Supply
Power Consumption
(Reference Value)
Operating
Temperature
Dimensions
Weight
Standard Accessory
Optional Accessory
* Refer to "Specification of Probes" on page 15.
Airflow Transducer (without / with Display)
6332 / 6332D
Clean Airflow
To select either current or voltage output (Selected with the dip switch).
-Current output: DC 4-20mA (Max. load resistance: 250Ω)
-Voltage output: DC 0-5V (Load impedance 5kΩor higher)
To be selected from the followings (Selected with the dip switch).
0-2.00, 0-5.00, 0-10.0, 0-25.0, or 0~50.0m/s
Depends on output range setting, measurement range and number of digit change.
-Output range setting: When 0 -2.00 / 0 -5.00 / 0 - 10.0 m/s
 Display resolution: 0.01m/s
-Output range setting: When 0 - 25.0 / 0 - 50.0m/s
 Display resolution: 0.1m/s
DC 12-24V
Approx. 2.0W (Under the following conditions- power supply: 12V, air velocity:
approx. 10m/s, using a main unit with a display and probe model 0965-03)
Power consumption rate is subject to change according to conditions such as air
velocity, probe type, and use of display.
-10 to 50 degree Celsius (No condensation)
Approx. 128 (W) × 78 (D) × 30 (H) mm
Approx. 320g
Operation Manual : 1
Main Unit Case:
1
Probe Cable (2m,5m,10m, 20m, 30m)
Dedicated AC Adapter (DC 12V output)
Ring Guard (For 0965-00 / 0965-21 / 0965-31)
Compression Fitting (For 0965-00 / 0965-01 / 0965-09 / 0965-10 / 0963-00)
14