Alarms And Notifications; Software Update - Nice FGSD-002 Instructions And Warnings For Installation And Use

Smoke and temperature sensor
Table of Contents

Advertisement

Notes:
Please use this procedure only in the event that the system primary controller is missing or otherwise inoperable.
Reset procedure should remove Smoke-Control from the Z-Wave network main controller's memory (depending on the controller's ver-
sion).
Removing the device from the Z-Wave network will reset Smoke-Control automatically.
8.7 - Operating through the Z-Wave network
Smoke-Control has a built in smoke detector and a temperature sensor, which makes it a multi channel device. Depending on the Z-Wave
controller, the device may show up as two devices (Smoke-Control and temperature sensor).
9
MENU MODE AND VISUAL INDICATIONS
Smoke-Control is equipped with a visual indicator for indicating and signaling the sensor's operating modes and alarms. In addition, the visual
indicator may inform of the Z-Wave network range or temperature threshold exceeded.
Visual indicator modes:
1. Alarms indications.
2. Added device status is signaled by a single green blink while inserting the battery.
3. Removed device status is signaled by a single red blink while inserting the battery.
4. Software update procedure is signaled by blinking in cyan
5. Successful software update is signaled with glowing in green
6. Unsuccessful software update is signaled with glowing in red
7. MENU levels are signaled with glowing in certain colour.
To enter MENU, press and hold the B-button for 3 seconds.
Once the indicator glows white, release the B-button. Visual indicator will then start changing colours in sequence. Each colour means differ-
ent MENU level. Transitions between the MENU levels will be signaled with a short beep as well. Press the B-button briefly to confirm choice.
Visual indicator colours will change in the following sequence:
WHITE - entering MENU + software update procedure,
GREEN - sending device state to associated devices,
VIOLET - Z-Wave range test,
YELLOW - device reset.
10

ALARMS AND NOTIFICATIONS

Smoke-Control indicates particular states as follows:
Fire alarm - three short beeps and visual indicator blinking red every 1,5 seconds (high priority)
Low battery alarm - short beep and visual indicator blinking yellow once per 50 seconds (normal priority)
Trouble alarm - short beep once per 50 seconds (normal priority)
Exceeding temperature threshold - short beep and visual indicator blinking blue once per specified time interval (parameter 31 - 10 sec-
onds by default) (low priority)
Lack of Z-Wave range - short beep and visual indicator blinking violet diode once per specified time interval (parameter 32 - 30 minutes by
default) (low priority)
Opened casing detection - short beep and visual indicator blinking white
Notes:
Except Fire, Low battery and Trouble alarm, the other notifications are by default disabled.
If more than one alarm is triggered, the alarm with the highest priority is signaled.
Smoke-Control automatically cancels fire alarms sent to the main Z-Wave network main controller and associated devices as well.
The casing opening notification cannot be cancelled through MENU.
11

SOFTWARE UPDATE

Smoke-Control features remote software update. Complete the following steps to perform device update:
1. Detach the sensor from its cover by turning the device counter-clockwise.
2. Make sure the device is located within direct range of the Z-Wave network controller.
3. Set the main controller into update mode (see controller's manual)
4. Press and hold the B-button for 3 seconds. The visual indicator will glow white. A short signal will sound.
5. Release the B-button.
6. Press the B-button briefly to confirm menu level choice (white visual indicator). The visual indicator blinking cyan will signal the update
process. The update process may take up to 10 minutes. During the update process, please do not remove the battery.