Download Print this page

Technical Specification; Trouble Shooting - Projoy Electric PEFS-24V-CN Series Installation Manual

Emergency rapid shutdown switch unit

Advertisement

RSD PEFS-PC Series

5 Technical Specification

Type
Operating AC Voltage Range
Norminal Frequency
Output Voltage
Output Current
24Vdc Control Cable Size
24Vdc Control Cable Length
With Standard Connectors
Spare Terminal Connectors
Maximum PEFS-PL80S-11
Maximum PEFS-PL80S-21
Dimensions(mm)
With Lock
Ambient Operating Temperature
Protection Class
Mounting
Max cable length

6 Trouble Shooting

Problem
PEFS-24V-CN power supply failure
PEFS-24V-CN switch activated
Panel (pair)
No PEFS-24V-CN switch output
voltage is 0V
PV Inverter
input 0V
String voltage
too low
In the occurrence of a fire, PROJOY recommend that all elements of the PEFS Rapid Shutdown system be assessed for
operational suitability by a competent person prior to re-energising.
PEFS-24V-C60
2.2A
60 Unites
30 Unites
210*175*105
Possible Cause
No mains supply
(LED OFF)
Broken cable
PV array not connected
Incorrect PEFS-24V-CN
polarity connection
No PEFS-24V-CN output
No DC isolator (if fitted)
input
DC Isolator (if fitted) OFF
Incorrect PEFS-24V-CN
polarity connection
PEFS-24V-C120 PEFS-24V-C240 PEFS-24V-C360 PEFS-24V-C340
100~240V AC
50/60 Hz
24V DC
4.4A
2* 4.4A
0.823 mm2 / 18 AWG
20 m / 30 m / 100 m
Yes
120 Unites
240 Unites
60 Unites
120 Unites
210*175*105
375*205*95
Optional
-30℃ ~ +70℃
IP65
Wall Mounted
250m (RSD cable length Excluded)
Possible Solution
Check area utility operational
Check mains ON
Check mains fuse
Check mains voltage between L&N marked terminals
Check 24VDC between + & - marked terminals
Turn red actuator anti-clockwise to release button
Check 24VDC between switch out terminal & PSU – marked terminal
Check 24VDC between terminals of remote AMP
Superseal connector (pin 1 +24VDC\pin 2 0VDC)
Check all PV to PEFS-24V-CN input connections
Check PV array Positive (+) goes to PEFS-24V-CN
Positive (+) and PV array Negative (-) goes to PEFS-PC Negative (-)
Replace PEFS-24V-CN
Check PEFS-24V-CN output connections
Check DC inputs to isolator
Turn DC Isolator ON
Check all PV array Positive (+) go to PEFS-PC
Positive (+) and PV array Negative (-) goes to PEFS-PC Negative (-)
3* 4.4A
4* 4.4A
360 Unites
480 Unites
180 Unites
240 Unites
375*205*95
375*205*160
www.projoy-electric.com
4

Advertisement

loading

This manual is also suitable for:

Pefs-24v-c60Pefs-24v-c120Pefs-24v-c240Pefs-24v-c360Pefs-24v-c340Rsd pefs-pc series