DIP SWITCH

Cleaning function
Rotation monitor
High speed*)
Low speed*)
*)
Manual operation (test mode)

OPERATIONAL INDICATIONS

On/alarm
Run
Rotation
Cleaning function connected in ON position.
When the rotor has stopped for 30 minutes, the cleaning function is
activated and the rotor rotates at minimum rpm for 10 seconds.
Rotation monitor set to ON position.
The rotor rotates at the set maximum rpm when the switch is set to ON.
After a test run, make sure the DIP switch is set to OFF.
The rotor rotates at the fixed minimum rpm when the switch is set to ON.
After a test run, make sure the DIP switch is set to OFF.
Lit with fixed light
It flashes when the control unit has tripped.
Comes on when the motor is to rotate, i.e. when the input signal exceeds
the threshold value.
Flashes when the magnet passes the magnetic sensor, regardless of the
"Rotation monitor" DIP switch setting.
Flashes even if the input signal is lower than the threshold value.