IBCcontrol MicroMax180 Manual

IBCcontrol MicroMax180 Manual

Control unit for rotary heat exchanger

Advertisement

Quick Links

MANUAL
Ska vara 25 mm i diameter på höjden
Set of EMC-glands as an option
CONTROL UNIT FOR ROTARY HEAT EXCHANGER
MicroMax180
Article no. F21018301
With adjustable boost function and threshold value
IBC
control

Advertisement

Table of Contents
loading

Summary of Contents for IBCcontrol MicroMax180

  • Page 1 MANUAL Ska vara 25 mm i diameter på höjden Set of EMC-glands as an option CONTROL UNIT FOR ROTARY HEAT EXCHANGER MicroMax180 Article no. F21018301 With adjustable boost function and threshold value control...
  • Page 3: Table Of Contents

    TABLE OF CONTENTS Installation instructions Mounting Safety instructions Manufacturer´s declaration Declaration of conformity Description of functions Technical data Functions - DIP switch - Operational indications - Alarms - Settings via potentiometer - Reset Connection diagram Connections Checks before powering up the control unit Putting the equipment into operation...
  • Page 4: Installation Instructions

    INSTALLATION INSTRUCTIONS Warning indication The control unit must be in perfect technical condition before use. Damage that can affect safety must be remedied immediately. Maintenance/Repairs The function of the control unit should be checked regularly. Troubleshooting and repairs may only be performed by trained personnel.
  • Page 5: Safety Instructions

    SAFETY INSTRUCTIONS The following symbols and references will be used in this description. These important instructions apply to personal protection and technical safety during operation. “Safety instructions” refers to instructions whose specific intent is to avoid the risk of personal injury and to prevent damage to equipment.
  • Page 6: Manufacturer´s Declaration Declaration Of Conformity

    Brännerigatan 5 A SE-263 37 Höganäs Sweden Tel: +46 42 33 00 10 Product Control unit for rotary heat exchanger Type designation MicroMax180 Applicable EMC Directive 2014/30/EU EU Directives Low Voltage Directive 2014/35/EU RoHS Directive 2011/65/EU including Delegated Directive EU2015/863 Applicable...
  • Page 7: Description Of Functions

    DESCRIPTION OF FUNCTIONS The MicroMax180 is part of a range of control units adapted, with the necessary • additional functions, for optimum control of rotary heat exchangers. The series consists of five sizes, MicroMax, MicroMax180, MicroMax370, MicroMax750 and MicroMax1500. All of the control units drive three-phase asynchronous motors with associated gearing, the control unit designation denotes motor output.
  • Page 8: Technical Data

    TECHNICAL DATA Connection voltage 1x230-240 V +/-15 % Ambient temperature, -25 - +45 50/60 Hz non condensing Power input, max. 390 W Protection form IP54 Input current, max. 1.7 A Weight 0.9 kg External fuse max. 10 A Dimensions, HxWxD 158x165x60 mm Exact value cannot be obtained with a digital measuring Output voltage*)
  • Page 9: Dip Switch

    DIP SWITCH Cleaning function Cleaning function connected in ON position. When the rotor has stopped for 30 minutes, the cleaning function is activated and the rotor rotates at minimum rpm for 10 seconds. Rotation monitor Rotation monitor set to ON position. High speed*) The rotor rotates at the set maximum rpm when the switch is set to ON.
  • Page 10: Alarms

    Alarms and trips in the event of a phase-to-phase or phase-to-earth short circuit and overcurrent. Short circuit phase-phase or phase-earth (earth fault) MicroMax180 trips immediately. Probable fault cause - Motor winding fault Measure motor resistance, it should be identical on all phases.
  • Page 11: Settings Via Potentiometer

    Continued from previous page Overcurrent MicroMax180 limits the current at 2.4 A and trips then after 4-5 s. Probable fault cause - The motor is too small in relation to rotor diameter - Rotor rotation sluggish - Damaged motor, e.g. bearing fault Measure current.
  • Page 12: Connection Diagram

    CONNECTION DIAGRAM U V W 13 14 15 9 10 1x 230 V 3 x 230 V Thermal Alarm relay 0 -10 V Rotation contact monitor (Max 2 A / 250 V AC) CONNECTIONS Switch off power before starting work on the equipment. Recommended tightening torque on terminals 0.5 Nm, max tightening torque 0.8 Nm.
  • Page 13: Checks Before Powering Up The Control Unit

    CHECKS BEFORE POWERING UP THE CONTROL UNIT Check that the control unit is connected as per instructions on page 10. Connection voltage 230-240 V +/-15%, 50/60 Hz. Check that the motor is wired for 3x230 V. If there is an operating switch between the motor and the control unit, the motor thermal contact should be connected via the auxiliary terminal in the operating switch.
  • Page 14: Emc Installation

    EMC INSTALLATION Connection voltage 3G1.5 Rotation monitor, LiYCY 2x0.34 Not shielded Shielded Motor Input signal, LiYCY 2x0.34/0.5 Ölflex Classic 110 CY/7G0.75 Shielded Shielded EMC glands must be used for shielded cables. The above cables or equivalent must be used to comply with the EMC Directive. EMC GLAND NOTE! When connecting the shield to the EMC gland, it is important to do so as shown above.
  • Page 15: Personal Notes

    PERSONAL NOTES...
  • Page 16 IBC control AB Brännerigatan 5 A SE-263 37 Höganäs Sweden Tel. +46 42 33 00 10 www.ibccontrol.se info@ibccontrol.se...