DESCRIPTION OF FUNCTIONS

The MicroMax180 is part of a range of control units adapted, with the necessary
additional functions, for optimum control of rotary heat exchangers.
The series consists of five sizes, MicroMax, MicroMax180, MicroMax370,
MicroMax750 and MicroMax1500.
All of the control units drive three-phase asynchronous motors with associated
gearing, the control unit designation denotes motor output.
All control units have an input signal of 0-10 V.
MicroMax180 is designed for rotors up to 2500 mm with a rotor speed of
max 12 rpm.
If a faster rotor speed is necessary, rotor diameter should be reduced.
Heat exchanger rpm and thus thermal efficiency are governed by the control unit
so that rotor speed is proportional to the input signal from the control centre.
MicroMax180 has a adjustable threshold value of 0-2 V.
MicroMax180 has adjustable boost function.
MicroMax180 has a rotation monitor (magnet mounted on the rotor with
associated magnetic sensor) and built-in cleaning function.
The functions can be disconnected via DIP switches.
MicroMax180 starts automatically following voltage
drop-out and resets all alarms on restart.
The motor should not be disconnected from the control unit while under load.