Connection Diagram; Connections - IBCcontrol MicroMax180 Manual

Control unit for rotary heat exchanger
Table of Contents

Advertisement

CONNECTION DIAGRAM

L N
1x 230 V

CONNECTIONS

Switch off power before starting work on the equipment.
Recommended tightening torque on terminals 0.5 Nm, max tightening torque 0.8 Nm.
Connection voltage
(L-N-PE)
Motor
(U-V-W)
Thermal contact
(T-T)
Alarm relay
(13-14-15)
Input signal
(2-3)
Rotation monitor
(9-10)
U V W
T
T
1
2
4
5
3
M
3 ~
3 x 230 V
Thermal
contact
(Max 2 A / 250 V AC)
1x230-240 V +/-15 %, 50/60 Hz.
NOTE! Protective earth must always be connected.
Three-phase asynchronous motor wired for 3x230 V (Delta).
Max 180 W.
Direction of rotation is changed by switching two of the phases.
The thermal contact in the motor should be used to protect the motor
from overheating.
Must be jumped if the temperature switch is not connected.
Closes between 14-15 in the event of an alarm or voltage drop-out.
Max 2 A resistive load / 250 V AC.
0-10 V.
Plus connected to terminal 2, minus to terminal 3.
White cable connected to terminal 9, brown to terminal 10.
The magnet is installed with south side (S) towards the sensor.
Max. gap 15 mm.
13 14 15
2 3
+
Alarm relay
0 -10 V
10
9 10
br
w
S
Rotation
monitor