ASEA AC36V-1 Operation Manual

ASEA AC36V-1 Operation Manual

Single and three phase yacht power converters
Table of Contents

Advertisement

Quick Links

Operations Manual
for the ASEA Power Systems
Models AC36V-1, AC36V-3, AC45V-1,
AC45V-3, AC54-1, and AC54V-3
Single and Three Phase Yacht Power Converters
P/N 604052, Revision B
Issued 12/11/2008

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the AC36V-1 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for ASEA AC36V-1

  • Page 1 Operations Manual for the ASEA Power Systems Models AC36V-1, AC36V-3, AC45V-1, AC45V-3, AC54-1, and AC54V-3 Single and Three Phase Yacht Power Converters P/N 604052, Revision B Issued 12/11/2008...
  • Page 2: Certification

    LIFE SUPPORT POLICY ASEA Power Systems does not authorize the use of any of its products or systems for use an AC voltage supply (source) for life support systems. Life support systems are devices which support or sustain life, and whose failure to perform, when properly used in accordance with this Operations Manual, can be reasonably expected to result in significant injury to the user.
  • Page 3: Using This Manual

    It is important that the operator reads this manual prior to installing and operating the converter. A thorough understanding of the information covered in this manual is required for proper installation and operation. If any questions arise while reading this manual, the user is encouraged to call ASEA Power Systems. ASEA Power Systems is located at:...
  • Page 4: Table Of Contents

    AC36V-1, -3 / AC45V-1, -3 / AC54V-1, -3 Operations Manual..TABLE OF CONTENTS CERTIFICATION ...........................2 WARRANTY ..........................2 USING THIS MANUAL .....................3 SAFETY NOTICES ......................6 INTRODUCTION TO THE AC36V, AC45V, AND AC54V ..........8 SPECIFICATIONS ......................10 ELECTRICAL SPECIFICATIONS ..............10 4.1.1 Input Service ....................10 4.1.2 Output Service ...................10...
  • Page 5 AC36V-1, -3 / AC45V-1, -3 / AC54V-1, -3 Operations Manual..SOFTWARE FEATURES ....................38 GENERAL ......................38 LOAD MANAGEMENT ..................38 LOAD MANAGEMENT OPERATION ...............40 7.3.1 Shore Cord Alarm, Single, Master, and Slave converters ......40 7.3.2 Shore Cord Setup, Single, Master, or Slave Converters ......41 7.3.3 Load Sharing, Slave converters with Shore Cord Management Option ..42...
  • Page 6: Safety Notices

    AC36V-1, -3 / AC45V-1, -3 / AC54V-1, -3 Operations Manual..SAFETY NOTICES Each shore power converter is capable of transferring large amounts of electrical energy very quickly. This quality is fundamental to a high performance power converter. International symbols are used throughout this manual to stress important information. Read the text below each symbol carefully and use professional skills and prudent care when performing the actions described by the text.
  • Page 7 AC36V-1, -3 / AC45V-1, -3 / AC54V-1, -3 Operations Manual.. THIS EQUIPMENT CONTAINS HIGH ENERGY, LOW IMPEDANCE CIRCUITS! LETHAL POTENTIALS ARE CONTAINED WITHIN THE SYSTEM EVEN WHEN IT IS APPARENTLY NOT OPERATING.  CARE MUST BE EXERCISED WHEN SERVICING THIS EQUIPMENT IN ORDER TO PREVENT SERIOUS OPERATOR INJURY OR EQUIPMENT DAMAGE.
  • Page 8: Introduction To The Ac36V, Ac45V, And Ac54V

    AC36V-1, -3 / AC45V-1, -3 / AC54V-1, -3 Operations Manual..INTRODUCTION TO THE AC36V, AC45V, AND AC54V Each model is a high performance Yacht Power Converter utilizing dual-conversion technology. The systems will accept any single or three phase input service with a frequency between 40- 70Hertz, and a voltage between 170-520VAC.
  • Page 9 AC36V-1, -3 / AC45V-1, -3 / AC54V-1, -3 Operations Manual..Being a converter designed from the ground up specifically for the yachting industry, all efforts have been made to produce a system capable of withstanding the marine environment. All system components are packaged in one drip-proof, dust-resistant stainless steel enclosure.
  • Page 10: Specifications

    AC36V-1, -3 / AC45V-1, -3 / AC54V-1, -3 Operations Manual..SPECIFICATIONS ELECTRICAL SPECIFICATIONS Parameter AC36V-1, -3 AC45V-1, -3 AC54V-1, -3 4.1.1 Input Service Input Power Form Single or Single of Three Phase Single or Three Phase Three Phase Input Voltage Range...
  • Page 11 AC36V-1, -3 / AC45V-1, -3 / AC54V-1, -3 Operations Manual..SPECIFICATIONS ELECTRICAL SPECIFICATIONS cont. 4.1.2 Output Service, cont. Table 1 - Output Current, Rated Continuous RMS Output Form AC36V-1 AC45V-1 AC54V-1 1Ø, 220V 164A /Ø 205A /Ø 245A /Ø 1Ø, 230V 156A /Ø...
  • Page 12: Control, Metering, And Status

    AC36V-1, -3 / AC45V-1, -3 / AC54V-1, -3 Operations Manual..SPECIFICATIONS, cont. ELECTRICAL SPECIFICATIONS, cont. 4.1.3 Control, Metering, and Status Input Power Control Input Service Disconnect Switch, 2 pos. Shore Power Control Membrane Switch, Input ON/OFF Control Converter Power Control Membrane Switch, Output ON/OFF Control, Ship’s Power Control...
  • Page 13: Installation

    AC36V-1, -3 / AC45V-1, -3 / AC54V-1, -3 Operations Manual..INSTALLATION The installation section is divided into two parts. The first will cover mechanical installation, the second, electrical installation. Read this manual thoroughly prior to attempting the installation. Improper installation is the most significant cause of system start-up problems and service issues over the product’s life.
  • Page 14: Mechanical Installation

    AC36V-1, -3 / AC45V-1, -3 / AC54V-1, -3 Operations Manual..MECHANICAL INSTALLATION The converters were designed for deck mount installations and as such are provided with six mounting holes, three per side. Mounting holes have been provided with ½” (12.7mm) diameters;...
  • Page 15: Mechanical Outline

    AC36V-1, -3 / AC45V-1, -3 / AC54V-1, -3 Operations Manual..MECHANICAL INSTALLATION, cont. FIGURE 2 MECHANICAL OUTLINE...
  • Page 16: Controls

    AC36V-1, -3 / AC45V-1, -3 / AC54V-1, -3 Operations Manual..MECHANICAL INSTALLATION, cont. FIGURE 3 CONTROLS...
  • Page 17: Electrical Installation

    AC36V-1, -3 / AC45V-1, -3 / AC54V-1, -3 Operations Manual..ELECTRICAL INSTALLATION This procedure assumes the physical installation of the converter has been completed. It is the users responsibility to provide input service over-current protection and disconnect means. Follow the table below for shore power wiring.
  • Page 18: Input Power Connections

    AC36V-1, -3 / AC45V-1, -3 / AC54V-1, -3 Operations Manual..5.2.1 Input Power Connections The converter is supplied with compression type terminal blocks for input power connections. These terminal blocks accept wires in the range of 250MCM to 6AWG. Refer to the applicable standards for selection of required wire gauge and type.
  • Page 19: Output Power Connections

    AC36V-1, -3 / AC45V-1, -3 / AC54V-1, -3 Operations Manual..5.2.2 Output Power Connections Each system is supplied with compression type terminal blocks for output power connections. These terminal blocks accept wires in the range of 250MCM to 6AWG. Refer to the applicable standard for selection of the required wire gauge and type.
  • Page 20: Seamless Transfer Connections

    AC36V-1, -3 / AC45V-1, -3 / AC54V-1, -3 Operations Manual..5.2.3 Seamless Transfer Connections If the Seamless Transfer Option was ordered with the system, connections must be made between the generator and the converter. These connections are used by the converter to successfully manage the seamless transfer operation and are comprised of control, signal, and feedback functions.
  • Page 21: Seamless Transfer Pcb Connections

    AC36V-1, -3 / AC45V-1, -3 / AC54V-1, -3 Operations Manual..5.2.3 Seamless Transfer Connections, cont. FIGURE 5 SEAMLESS TRANSFER PCB CONNECTIONS...
  • Page 22: Multi-Cabinet

    AC36V-1, -3 / AC45V-1, -3 / AC54V-1, -3 Operations Manual..5.2.4 Multi-Cabinet System Interconnection All multi-cabinet systems are constructed from one cabinet which serves as the system Master, and a second cabinet which serves as the Slave. A paralleling cable assembly (P/N 605150) is shipped pre-connected to the Slave cabinet and coiled at the base of the cabinet near the Input and Output connection terminal blocks.
  • Page 23: Operation

    AC36V-1, -3 / AC45V-1, -3 / AC54V-1, -3 Operations Manual..OPERATION POWER TURN-ON PROCEDURE Close the shore power (input) circuit breaker or switch to the converter. Turn the disconnect (14) switch to the ON position. After 1-3 seconds, fans will be heard, and the display will become active.
  • Page 24 AC36V-1, -3 / AC45V-1, -3 / AC54V-1, -3 Operations Manual..POWER TURN-ON PROCEDURE, cont. The display will sequence to the SUMMARY DISPLAY indicating the converter’s operational state. Both input and output (converter) should indicate OFFLINE at this time. Press the INFO (13) button to review the Shore Power state if desired.
  • Page 25: Systems Without Seamless Transfer

    AC36V-1, -3 / AC45V-1, -3 / AC54V-1, -3 Operations Manual..POWER TURN-ON PROCEDURE, cont. Press the CONVERTER POWER (4) button and the screen will now change. As with the shore power displays, the F1-F4 (13) buttons will cycle through a variety of converter power data. Output voltages and currents should indicate zero.
  • Page 26: Systems With Seamless Transfer

    AC36V-1, -3 / AC45V-1, -3 / AC54V-1, -3 Operations Manual..POWER TURN-ON PROCEDURE, cont. 6.1.2 Systems Equipped With The Seamless Transfer Option With the converter in the Standby State (as left at the end of Section 6.1), press the GENERATOR POWER (3) display button.
  • Page 27 AC36V-1, -3 / AC45V-1, -3 / AC54V-1, -3 Operations Manual..POWER TURN-ON PROCEDURE, cont. 6.1.2 Systems Equipped With The Seamless Transfer Option, cont. If the generator is supplying power to the ship, the SHIP’S POWER - GENERATOR LED (12A) is lit, and the GENERATOR metering display indicates approximately the same voltage as the CONVERTER metering display, then proceed by pressing the SHIP’S POWER - CONVERTER...
  • Page 28: Multi-Cabinet Operation

    AC36V-1, -3 / AC45V-1, -3 / AC54V-1, -3 Operations Manual..MULTI-CABINET OPERATION Multi-cabinet systems are operated from the Master’s control panel. Each cabinet retains its own control panel and metering display for individual monitoring. A load management option exists that allows individual cabinets to load according to shore cord size (see section 7 for details).
  • Page 29: Auto-Restart Feature

    AC36V-1, -3 / AC45V-1, -3 / AC54V-1, -3 Operations Manual..AUTO-RESTART FEATURE The Auto-Restart feature will safely and automatically bring the shore power converter back on- line following a power failure and recovery event. Highlights include:  Automatically routes power from the dock to the ships power buss.
  • Page 30: Operation

    AC36V-1, -3 / AC45V-1, -3 / AC54V-1, -3 Operations Manual..AUTO-RESTART FEATURE, cont. 6.3.1 Operation Auto-Restart must be enabled from the converter front panel by simultaneously pressing two buttons. Anytime the system status is “FAILURE,” the converter will disable the Auto-Restart feature.
  • Page 31: Turn-Off Procedure

    AC36V-1, -3 / AC45V-1, -3 / AC54V-1, -3 Operations Manual..TURN-OFF PROCEDURE 6.4.1 Systems Not Equipped With The Seamless Transfer Option Transfer power from the converter to the generator. This must be performed in a “break-before- make” method, that is, at no time can the generator(s) and shore power converter be operated in parallel.
  • Page 32: Systems With Seamless Transfer

    AC36V-1, -3 / AC45V-1, -3 / AC54V-1, -3 Operations Manual..6.4.2 Systems Equipped With The Seamless Transfer Option The generator must be started and be prepared to accept the ship’s electrical loads. Measure the generator voltage using the converter’s metering display, selecting the GENERATOR POWER (3) function.
  • Page 33: Remote Communication

    The Baud Rate can be increased by pressing the F1 (13) button, and decreased by pressing the F2 (13) button. Pressing SYSTEM STATUS (5) saves the setting. Standard baud rates are 1200, 2400, 4800, 9600, 19200, and 38400 where 19200 is the standard for communication with ASEA Power Systems Touch Screens.
  • Page 34: Rs-232C Pinout

    AC36V-1, -3 / AC45V-1, -3 / AC54V-1, -3 Operations Manual..REMOTE COMMUNICATIONS, cont. FIGURE 7 RS-232C PINOUT...
  • Page 35 AC36V-1, -3 / AC45V-1, -3 / AC54V-1, -3 Operations Manual..REMOTE COMMUNICATIONS, cont. Remote control can be accomplished with the use of an ASEA Power Systems defined Remote Communication Command Set, or through visual touch screen software that is described elsewhere.
  • Page 36 AC36V-1, -3 / AC45V-1, -3 / AC54V-1, -3 Operations Manual..REMOTE COMMUNICATIONS, cont. Command Description Comment :SHORe:ON Shore Power ON Same as pressing the Shore Power ON button on the panel. :SHORe:OFF Shore Power OFF Same as pressing the Shore Power OFF button on the panel.
  • Page 37 AC36V-1, -3 / AC45V-1, -3 / AC54V-1, -3 Operations Manual..REMOTE COMMUNICATIONS, cont. Command Description Return Value Range :MEASure:SP1:CURRent1 Shore Power A RMS Current Real number, 0 to 1000 :MEASure:SP1:CURRent2 Shore Power B RMS Current Real number, 0 to 1000...
  • Page 38: Software Features

    SOFTWARE FEATURES GENERAL ASEA Power Systems' shore power converters provide a variety of software-based resources. Each major function is described in detail in the following pages. BOLD upper-case text indicates when a display button is being referenced. Where two buttons are given as BUTTON + BUTTON, the buttons must be pressed simultaneously.
  • Page 39 AC36V-1, -3 / AC45V-1, -3 / AC54V-1, -3 Operations Manual..LOAD MANAGEMENT, cont. Load Sharing The slave converter of a paralleled converter system can be forced to draw less current than the master converter, if attached to a shore cord with lesser available power due to lower amperage, lower voltage, or different form (i.e.
  • Page 40: Load Management Operation

    AC36V-1, -3 / AC45V-1, -3 / AC54V-1, -3 Operations Manual..LOAD MANAGEMENT OPERATION 7.3.1 Shore Cord Alarm, Single, Master, and Slave converters If the yacht’s electrical system includes a power management or load-shed feature, the Shore Cord Alarm can be used to effect a change in loading when the converter reaches a programmed load threshold, or simply draw the yacht engineer’s attention.
  • Page 41: Shore Cord Setup, Single, Master, Or Slave Converters

    AC36V-1, -3 / AC45V-1, -3 / AC54V-1, -3 Operations Manual..LOAD MANAGEMENT OPERATION, cont. 7.3.2 Shore Cord Setup, Single, Master, or Slave Converters The Shore Cord Setup screen is used to set the actual shore cord ampacity based on the marina’s dock or pedestal circuit breaker.
  • Page 42: Load Sharing, Slave Converters With Shore Cord Management Option

    AC36V-1, -3 / AC45V-1, -3 / AC54V-1, -3 Operations Manual..LOAD MANAGEMENT OPERATION, cont. 7.3.3 Load Sharing, Slave converters with Shore Cord Management Option The function of this special Slave converter screen includes those functions of the normal Shore Cord Setup screen described on the previous page with one addition: Load Sharing between the two converters of a paralleled converter system is controlled by entering the MASTER CAPACITY here.
  • Page 43 AC36V-1, -3 / AC45V-1, -3 / AC54V-1, -3 Operations Manual..LOAD MANAGEMENT OPERATION, cont. 7.3.3 Load Sharing, Slave converters with Shore Cord Management Option, cont. From the front panel, press the SHORE POWER + F2 buttons, and then Cord (F1) to access the...
  • Page 44: Voltage Droop, Single Or Master Converters

    AC36V-1, -3 / AC45V-1, -3 / AC54V-1, -3 Operations Manual..LOAD MANAGEMENT OPERATION, cont. 7.3.4 Voltage Droop, Single or Master Converters Upon Shore Alarm, the Voltage Droop feature may be used to save up to 10% converter capacity by reducing the converter output voltage up to 5%. This is offered as a solution where the yacht does not already have power management and load-shed capabilities that can be triggered with the Shore Cord Alarm signal.
  • Page 45: Automatic Transfer To Generator, Single Or Master Converters (Seamless Transfer Installed)

    AC36V-1, -3 / AC45V-1, -3 / AC54V-1, -3 Operations Manual..LOAD MANAGEMENT OPERATION, cont. 7.3.5 Automatic Transfer to Generator, Single or Master Converters (Seamless Transfer installed) Upon Shore Alarm, the Automatic Transfer to Generator feature may be used to perform a Seamless Transfer to a pre-selected generator.
  • Page 46: Quick Setup Of Shore Cord Alarm, Single, Master, Or Slave Converters

    AC36V-1, -3 / AC45V-1, -3 / AC54V-1, -3 Operations Manual..LOAD MANAGEMENT OPERATION, cont. 7.3.6 Quick Setup of Shore Cord Alarm, Single, Master, or Slave Converters 1. Turn on the red Disconnect switch of both converters and wait 15-20 seconds for initialization.
  • Page 47: Expert Load Sharing Use, Paralleled Converters

    AC36V-1, -3 / AC45V-1, -3 / AC54V-1, -3 Operations Manual..LOAD MANAGEMENT OPERATION, cont. 7.3.7 Expert Load Sharing Use, Paralleled Converters The Load Sharing system described in this document has been programmed for simple use and comprehensive gathering of all pertinent data into a few, simple screens. However, the controls can be bypassed and Load Sharing implemented by the user directly via the Slave’s programmable...
  • Page 48: Generator Frequency Analysis

    AC36V-1, -3 / AC45V-1, -3 / AC54V-1, -3 Operations Manual..GENERATOR FREQUENCY ANALYSIS Press the SYSTEM STATUS + GENERATOR POWER buttons to access the Generator Frequency Analysis Display. Used for observing lifetime generator frequency range. GENERATOR FREQUENCY ANALYSIS DISPLAY Generator MIN Frequency: XX.XXHz...
  • Page 49: Agc Control

    AC36V-1, -3 / AC45V-1, -3 / AC54V-1, -3 Operations Manual..AGC CONTROL Press the SHORE POWER + F4 buttons to access the Automatic Gain Control (AGC) CONTROL display. AGC CONTROL SCREEN Automatic Gain Control is: ENABLED Enable Disable Exit This function enables or disables AGC. Press the Enable (F1) button to enable the feature, the Disable (F2) button to disable the feature, and the Exit (F5) button to save the settings and exit.
  • Page 50: Kw-Hour Meter And Maximum Power Level Display

    AC36V-1, -3 / AC45V-1, -3 / AC54V-1, -3 Operations Manual..kW-HOUR METER AND MAXIMUM POWER LEVEL DISPLAY Press the SHORE POWER + CONVERTER POWER buttons to access the Automatic KW- HOUR METER and maximum power level display. KW-HOUR METER kW-Hours:XXXXXXX.XX Run Time. XX:XX:XX:XX Max.
  • Page 51: Converter Output Voltage Control

    AC36V-1, -3 / AC45V-1, -3 / AC54V-1, -3 Operations Manual..CONVERTER OUTPUT VOLTAGE CONTROL Press the CONVERTER POWER + F5 buttons to access the CONVERTER OUTPUT VOLTAGE CONTROL display. CONVERTER OUTPUT VOLTAGE CONTROL Vout = XXX.X More Less XXXV Exit This function allows the user to increase or decrease the converter output voltage (Vout).
  • Page 52: Event Log

    AC36V-1, -3 / AC45V-1, -3 / AC54V-1, -3 Operations Manual..EVENT LOG Press the EVENT LOG (or CALIBRATE on older converters) button to access the EVENT LOG display. EVENT LOG CONTROL SCREEN F1: EVENT LOG VIEWER XXXX Events F2: EVENT LOG TRACKER F3: EVENT LOG REGISTRY This is for monitoring internal converter logic operation.
  • Page 53 AC36V-1, -3 / AC45V-1, -3 / AC54V-1, -3 Operations Manual..EVENT LOG, cont. Press the F3 button to access the EVENT LOG REGISTRY display. EVENT LOG REGISTRY PRESS: ‘SHORE POWER’ to edit Registry, The ‘F1’ for log On & ‘F2’ for log Off.
  • Page 54: Diagnostics

    AC36V-1, -3 / AC45V-1, -3 / AC54V-1, -3 Operations Manual..DIAGNOSTICS As previously described in paragraph 6.1, the converter’s LCD display will initiate on turn-on in the SUMMARY DISPLAY indicating the converter’s operational state. Return to this screen at any time by pressing the SYSTEM STATUS (5) button.
  • Page 55 AC36V-1, -3 / AC45V-1, -3 / AC54V-1, -3 Operations Manual..DIAGNOSTICS, cont. To aid in system diagnostics, three status words have been provided in the STATUS WORD DISPLAY which is accessed by pressing the SYSTEM STATUS (5) and F2 (13) buttons simultaneously.
  • Page 56: Status Word Bit Definitions

    AC36V-1, -3 / AC45V-1, -3 / AC54V-1, -3 Operations Manual..DIAGNOSTICS, cont. FIGURE 8 STATUS WORD BIT DEFINITIONS...
  • Page 57: Calibration

    AC36V-1, -3 / AC45V-1, -3 / AC54V-1, -3 Operations Manual..CALIBRATION In an uncalibrated state the input and output voltage and input current metering system should be within 5%. The uncalibrated output current meter is normally 10% low. For calibration an external reference voltmeter will be required along with a calibrated current transformer or probe.
  • Page 58 AC36V-1, -3 / AC45V-1, -3 / AC54V-1, -3 Operations Manual..CALIBRATION, cont. Generator Power Calibration - Use an external reference voltmeter to measure the generator voltage at the generator terminals located on TB12-1, 2, 3, 4. To enter the meter calibration screen, press and hold the GENERATOR POWER (3) button down for 7 seconds, or until the calibration display appears, then release the button.
  • Page 59: Maintenance

    AC36V-1, -3 / AC45V-1, -3 / AC54V-1, -3 Operations Manual..MAINTENANCE Due to the design and construction of the converter, preventative maintenance is held to a modest level. The following table lists minimum recommended tasks and frequency. TASK FREQUENCY COMMENTS...
  • Page 60: International Power Form Reference

    AC36V-1, -3 / AC45V-1, -3 / AC54V-1, -3 Operations Manual..INTERNATIONAL POWER FORM REFERENCE Country Frequency Nominal Voltage Comments American Samoa 60Hz 120/240 277/480 Antigua 60Hz 230/400 Argentina 50Hz 220/380 Aruba 60Hz 127/220 115/230 Australia 50Hz 240/415 250/435 Azores 50Hz...
  • Page 61 AC36V-1, -3 / AC45V-1, -3 / AC54V-1, -3 Operations Manual..250/440 Benin 50Hz 220/380 Bermuda 60Hz 120/240 120/208 Brazil 60Hz 115/230 127/220 220/380 Brunei 50Hz 240/415 Bulgaria 50Hz 220/380 Burma 50Hz 230/400 Canada 60Hz 120/240 120/208 277/480 Canary Islands 50Hz...
  • Page 62 AC36V-1, -3 / AC45V-1, -3 / AC54V-1, -3 Operations Manual..Costa Rica 60Hz 120/240 120/208 Cyprus 50Hz 240/415 Denmark 50Hz 220/380 Dominica 50Hz 230/400 Dominican 60Hz 120/240 Republic 120/208 Ecuador 60Hz 120/240 120/208 Fiji 50Hz 240/415 Finland 50Hz 220/380 France...
  • Page 63 AC36V-1, -3 / AC45V-1, -3 / AC54V-1, -3 Operations Manual..Guatemala 60Hz 120/208 Haiti 60Hz 110/220 120/208 Honduras 60Hz 110/220 120/208 Hong Kong 50Hz 220/380 Ireland 50Hz 220/380 Israel 50Hz 230/400 Italy 50Hz 127/220 220/380 Jamaica 50Hz 110/220 Japan 50Hz...
  • Page 64 AC36V-1, -3 / AC45V-1, -3 / AC54V-1, -3 Operations Manual..Mauritius 50Hz 230/400 Mexico 60Hz 127/220 Monaco 50Hz 127/220 220/380 Montserrat 60Hz 230/400 Morocco 50Hz 127/220 220/380 Netherlands 50Hz 220/380 Netherlands 50Hz 127/220 Antilles 220/380 60Hz 120/240 New Caledonia 50Hz...
  • Page 65 AC36V-1, -3 / AC45V-1, -3 / AC54V-1, -3 Operations Manual..St. Lucia 50Hz 240/415 St. Vincent 50Hz 230/400 Saudi Arabia 60Hz 127/220 Seychelles 50Hz 240/415 Sierra Leone 50Hz 230/400 Singapore 50Hz 230/400 South Africa 50Hz 220/380 Spain 50Hz 127/220 220/380...
  • Page 66 AC36V-1, -3 / AC45V-1, -3 / AC54V-1, -3 Operations Manual..United Kingdom 50Hz 240/415 Uruguay 50Hz 220/380 Venezuela 60Hz 120/240 120/208 Amer. Virgin 60Hz 120/240 Islands 120/208...