AL-KO EASYAIR flat GF-01 Operating And Assembly Instruction Manual page 31

Flat air handling unit
Table of Contents

Advertisement

Assembly
Fans
Open or fit the maintenance panel, see "5.4 Opening/removing the maintenance panel" on page 23.
Disconnect the electric cable by unfastening the plug-in connection.
Position the component lock in the slot with a 90° rotation.
Carefully remove the fan from the housing.
Plate heat exchanger (counterflow)
Open or fit the maintenance panel, see "5.4 Opening/removing the maintenance panel" on page 23.
Support the door rib from below.
Unfasten the screws on the door rib.
Carefully take out the door rib and modules of the plate heat exchanger (countercurrent) from the housing and re-
move them individually.
Fig. 19 Remove door rib
1
Door rib
2
GF module
3
Tooth disc
3059570
Risk of injury due to slipping parts.
The blocks on the door ribs are secured against falling.
By moving the door ribs horizontally, prevent the blocks lying on them from slipping off.
Wear personal protective equipment.
Subject to changes in line with technical progress.
CAUTION
4
DUO-Taptite M5x10
5
Covering cap
5
4
3
1
2
31