Figure 27
Effect of Changing the System Voltage Setting
Auto Start Volt: The 6VSG will automatically start when the battery bank voltage has reached or fallen below this value for 180
seconds (3 minutes). Default settings are shown in Figure 28.
Nominal Voltage
Default System Voltage, VDC
Figure 28
Auto Start Voltage
Note:
The 3-minute (180-second) time delay can be changed using a personal computer (laptop) and Kohler
Contact a Kohler authorized distributor or dealer to adjust the delay setting, if necessary.
Auto Stop Load: The auto stop load is set as a percentage of full load. As the battery bank approaches the fully charged state,
the charge rate slows, and the load on the generator set decreases. The 6VSG will automatically stop when the load has reached
or fallen below the Auto Stop Load setting for 180 seconds (3 minutes). The default setting is 40% load.
Load Limit ( %): This setting limits the current output to the maximum charge rate specified by the battery manufacturer or load
in the application. The default setting is 100%, which gives the maximum current values shown in Figure 29. Refer to the battery
manufacturer's recommended maximum charge rate and contact an authorized Kohler distributor or dealer if the setting needs
to be changed.
�������� ���������� =
Nominal Voltage
System Voltage, VDC
Maximum Current at 100% Load Limit, Amps
Figure 29
Maximum Charge Current at Default Load Limit Setting of 100%
42
24V
36V
48V
25
37.5
50
(���������������������� ���������������� �������������� (������) �� �������������� ���������������� �������������� (��������)) �� ������
24V
27
222
�������� ����������
36V
48V
40.5
54
148
111
KPS_104
SiteTech™ software.
®
TP-6843
12/21