Table 10F — Start-Up Failures: This is an alarm condition. A manual reset is required
to clear.
Primary
Secondary
Message
Message
Low Oil Pressure
Failure To
Start
Oil Press Sensor
Fault
Failure To
Start
Low Chilled
Failure To
Water Flow
Start
Low Condenser
Failure To
Water Flow
Start
Starter Fault
Failure To
Start
Starter Overload
Failure To
Trip
Start
Line Voltage
Dropout
Failure To
Start
High Condenser
Pressure
Failure To
Start
Excess Accelera-
Failure To
tion Time
Start
Alarm Message/Primary
Cause
OILPD [VALUE] exceeded limit
of [LIMIT]*. Check oil pump sys-
tem.
OILPD [VALUE] exceeded limit
of [LIMIT]*. Check oil pressure
sensor.
EVFL Evap Flow Fault: Check
water pump/flow switch.
CDFL Cond. Flow Fault: Check
water pump/flow switch.
STR FLT Starter Fault: Check
Starter for Fault Source.
STR FLT Starter Overload
Trip: Check amps calibration/
reset overload.
V P Single-Cycle Dropout
Detected: Check voltage sup-
ply.
High Condenser Pressure
[LIMIT]: Check switch 2C aux,
and water temperature/flow.
CA P Excess Acceleration:
Check guide vane closure at
start-up.
Additional Cause/Remedy
Check for closed oil supply valves.
Check oil filter. Check for low oil tem-
perature. Check transducer accuracy.
Check for excessive refrigerant in oil
sump. Run oil pump manually for 5 min-
utes. Check transducer calibration.
Check cooler pressure transducer cali-
bration. Check wiring. Replace trans-
ducer if necessary.
Check wiring to flow switch. Check
through Control Test for proper switch
operation.
Check wiring to flow switch. Check
through Control Test for proper switch
operation.
A starter protective device has faulted.
Check starter for ground fault, voltage
trip, temperature trip, etc.
Reset overloads before restart.
Check voltage supply. Check trans-
formers for supply. Check with utility if
voltage supply is erratic. Monitor must
be installed to confirm consistent, sin-
gle-cycle dropouts. Check low oil pres-
sure switch.
Check for proper design condenser flow
and temperature. Check condenser
approach. Check 2C auxiliary contacts
on oil sump starter. Check high pres-
sure switch.
Check that guide vanes are closed at
start-up. Check starter for proper opera-
tion. Reduce unit pressure if possible.