Mitsubishi Electric MSZ-GL06NA Service Manual page 30

Hide thumbs Also See for MSZ-GL06NA:
Table of Contents

Advertisement

MSZ-GL24NA
MSY-GL24NA
The indoor fan motor error has occurred, and the indoor fan does not operate.
Turn OFF the power supply.
Is there any foreign matter that inter-
feres the rotation of the line flow fan?
Yes
Remove the foreign matter and
adjust the line flow fan.
Is there 294/325 V DC
between CN211
and
(–) ?
No
Replace the indoor electronic control P.C.
board and the indoor terminal P.C. board.
The indoor fan motor error has occurred, and the indoor fan repeats "12-second ON and 30-second OFF" 3 times, and then stops.
Measure the voltage between
CN211
(+) and
(–) while the fan
motor is rotating.
OBH732D
Pay enough attention to the high voltage on the fan motor connector.
Turn ON the power supply, wait 5 seconds or more, and then press the
emergency operation switch.
Measure the supply voltage as follows within 12 seconds after the
emergency operation switch is pressed.
If more than 12 seconds passes, turn OFF the power supply and turn it
No
ON again, then measure the voltage. *
<Indoor electronic control P.C. board>
1. Measure the voltage between CN211
2. Measure the voltage between CN211
* If more than 12 seconds passes after the emergency operation switch is
pressed, the voltage measured at 2. above goes 0 V DC although the
indoor P.C. board is normal.
Does the voltage between CN211
(+) and
(–) on the indoor electronic
control P.C. board rise to the range of
(+)
Yes
3 to 6 V DC within 12 seconds after
the emergency operation switch is
pressed?
Replace the indoor electronic control
P.C. board.
Is it unchanged holding
0 or 15 V DC?
Replace the indoor fan motor.
(+) and
(+) and
Yes
No
Replace the indoor electronic
control P.C. board.
No
(Changed)
Yes
(Unchanged)
30
(–).
(–).
Replace the indoor fan motor.