BGH BV-V28W/DHN1 Manual page 95

Hide thumbs Also See for BV-V28W/DHN1:
Table of Contents

Advertisement

VRF 50/60Hz
installed too close to indoor unit lift pumps.
Air conditioner drain piping should be installed separately from waste, rainwater and other drain piping and should
not come into direct contact with the ground.
Drain piping diameter should be not less than the indoor units' drain piping connection.
To allow inspection and maintenance, the piping clamps shipped with units should be used to attach drain piping to
indoor units – adhesive should not be used.
Thermal insulation should be added to drain piping to prevent condensation forming. Thermal insulation should
extend all the way to the connection with the indoor unit.
Units with drain pumps should have separate drain piping systems from systems that use natural drainage.
5.2 Water Traps
For indoor units with a high negative pressure differential at the outlet of the
drainage pan, a trap should be fitted to the drain piping to prevent poor
drainage and/or water being blown back into the drainage pan. Traps should
be arranged as in Figure 3-5.6. The vertical separation H should be in excess of
50mm. A plug may be fitted to allow cleaning or inspection.
5.3 Selecting Piping Diameters
Select branch drainage piping (the drain piping connection to each unit)
diameters according to indoor unit flow volume and select main drainage piping diameters according to the combined
flow volume of the upstream indoor units. Use a design assumption of 2 liters of condensate per horsepower per hour. For
example, the combined flow volume of three 2HP units and two 1.5HP units would be calculated as follows:
Combined flow volume
Tables 3-5.1 and 3-5.2 specify the required piping diameters for horizontal and vertical branch piping and for main piping.
Note that main piping should use PVC40 or larger.
Table 3-5.1: Horizontal drain piping diameters
PVC piping
PVC25
PVC32
PVC40
PVC50
PVC63
94
Figure 3-5.5: Drain piping air vents
=
3
+
2
Nominal
diameter (mm)
Slope 1:50
25
32
40
50
63
x
2 L/HP/h × 2HP
x
2 L/HP/h × 1.5HP
Capacity (L/h)
Slope 1:100
39
27
70
50
125
88
247
175
473
334
Figure 3-5.6: Drain piping water traps
=
18 L/h
Remarks
Branch piping only
Branch or main piping