BGH BV-V28W/DHN1 Manual page 13

Hide thumbs Also See for BV-V28W/DHN1:
Table of Contents

Advertisement

VRF 50/60Hz
the required heat load is 10.5kW.
Provisionally select an outdoor unit using the sum of the capacity indexes (CIs) of the selected indoor units (as shown
in Table 1-5.5), ensuring that the combination ratio is between 50% and 130%. Refer to Table 1-5.6. As the sum of CIs
of the indoor units is 120. For the 10kW unit is not suitable, try to select 12kW unit.
The number of connected indoor units is 4 and the maximum number of connected indoor units on the 12kW outdoor
unit is 7, so the number of connected indoor units is within the limitation.
Calculate the corrected capacity of the outdoor unit:
a)
The sum of the indoor unit CIs is 120 and the CI of the 12kW outdoor unit is 120, so the combination ratio is 120 /
120 = 100%.
b)
Using the outdoor unit's cooling capacity table, interpolate to obtain the capacity ("B") corrected for outdoor air
temperature, indoor air temperature, and combination ratio. Refer to Tables 1-5.8 and 1-5.9.
Table 1-5.8: Extract from Table 2-7.3 BV-V42W/DHN1(At)
cooling capacity
Outdoor
CR
temp.
(°C DB)
100%
90%
c)
Find the correction factor for piping length and level difference ("K1")
Figure 1-5.4: Atom rate of change in cooling capacity
d)
Calculate the corrected capacity of BV-V42W/DHN1(At) ("C") by using K1:
The corrected capacity 10.84 kW is larger than required total heat load 10.5kW, so selection is complete.
12
Indoor air temp.
(°C DB / °C WB)
air
25.8 / 18.0
TC
kW
31
11.2
33
11.2
35
11.2
31
10.1
33
10.1
35
10.1
C = B × K1 = 11.2 × 0.968 =10.84kW
Table 1-5.9: Cooling capacity calculated by interpolation
CR
PI
kW
2.46
2.63
100%
2.80
2.11
2.26
90%
2.40
Indoor air temp.
Outdoor
(°C DB / °C WB)
air
25.8 / 18.0
temp.
TC
(°C DB)
kW
33
11.2
B = 11.2
33
10.1
PI
kW
2.76
2.37

Advertisement

Table of Contents
loading

Table of Contents