10.2. Precautions concerning piping
connection and valve operation
• Conduct piping connection and valve operation accurately and carefully.
•   R emoving the pinched connecting pipe
When shipped, a pinched connecting pipe is attached to the on-site liquid
and gas valves to prevent gas leakage.
Take the following steps 1 through 4 to remove the pinched connecting
pipe before connecting refrigerant pipes to the outdoor unit.
1 Check that the refrigerant service valve is fully closed (turned clockwise
all the way).
2 Connect a charging hose to the service port on the liquid/gas refrigerant
service valve, and extract the gas in the pipe section between the
refrigerant service valve and the pinched connecting pipe.
3 After vacuuming gas from the pinched connecting pipe, sever the
pinched connecting pipe at the location shown in [Fig.10.2.1] and drain
the refrigerant.
4 After completing 2 and 3 heat the brazed section to remove the
pinched connecting pipe.
[Fig. 10.2.1]
• P200, P250, P300
<A>
<B>
D
E
G
<A> Refrigerant service valve (liquid side/brazed type)
<B> Refrigerant service valve (gas side/brazed type)
Shaft
A
Fully closed at the factory, when connecting the piping, and when
vacuuming. Open fully after these operations are completed.
<When opening>
• Turn the shaft counterclockwise with a hexagonal wrench.
• Turn around the shaft until it stops.
<When closing>
• Turn the shaft clockwise with a hexagonal wrench.
• Turn around the shaft until it stops.
Shaft
B
Fully closed at the factory, when connecting the piping, and when
vacuuming.
Open fully after these operations are completed.
<When opening>
• Turn the shaft counterclockwise.
• Turn around the shaft until it stops.
<When closing>
• Turn the shaft clockwise.
• Turn around the shaft until it stops.
Stopper pin
C
Prevents the shaft from turning 90˚ or more.
Service port
D
Available for gas venting of the pinched connecting pipe, or vacuuming in the
refrigerant pipes on the site.
Cap
E
Remove the cap before operating the shaft. Be sure to return it to the original
position after completing the operation.
Pinched connecting pipe severing portion
F
Pinched connecting pipe brazing portion
G
• P350, P400, P450, P500
<A>
<B>
D
A
A
E
O
S
G
F
Warning:
• The sections between the refrigerant service valves and the pinched
connecting pipes are filled with gas and refrigerant oil. Extract the gas
and refrigerant oil in the above-mentioned pipe section before heating
the brazed section to remove the refrigerant service valve pinched
connecting pipe.
- If the brazed section is heated without first extracting the gas and
refrigerant oil, the pipe may burst or the pinched connecting pipe may blow
off and ignite the refrigerant oil, causing serious injury.
Caution:
• Place a wet towel on the refrigerant service valve before heating the
brazed section to keep the temperature of the valve from exceeding
120 ˚C.
• Direct the flame away from the wiring and metal sheets inside the unit
to prevent heat damage.
Caution:
• Do not vent R410A into the atmosphere.
• Refrigerant pipe connection
This product needs connecting pipes for front piping and bottom post-piping.
(Refer to [Fig.10.2.2])
Check the liquid/gas piping dimensions before connecting the refrigerant
pipe.
Refer to the table below for piping dimensions.
Make sure that the refrigerant pipe is not touching other refrigerants pipes,
unit panels, or base plates.
Be sure to use non-oxidative brazing when connecting pipes.
Be careful not to burn the wiring and plate when brazing.
B
<Refrigerant piping connection examples>
C
[Fig.10.2.2]
<A>
D
<C>
F
<E> Severing portion
referral figue
B
* Use a pipe cutter to sever.
<A> Front pipe routing
<C> Liquid side
<E> Severing portion referral figue
Refrigerant service valve piping
A
Severing portion
C
Model
Liquid
P200
ø9.52 Brazed
ø9.52 Brazed
P250
(ø12.7 Brazed) *1
ø9.52 Brazed
P300
(ø12.7 Brazed) *2, *3
P350
ø12.7 Brazed
ø12.7 Brazed
P400
(ø15.88 Brazed) *3
P450
ø15.88 Brazed
P500
*1 Furthest piping length (OU from IU)
*2 Furthest piping length (OU from IU)
*3 Indicates dimensions and connection specifications in the case the unit is
used in combination with other outdoor units.
<B>
<D>
<C>
A
D
C
<B> Bottom pipe routing
<D> Gas side
75mm (reference measurement)
B
Refrigerant service valve side
D
Diameter
Refrigerant pipe
Gas
Liquid
ø9.52
ø22.2 Brazed
ø12.7
ø28.58 Brazed
ø15.88
90m
40m
<D>
A
(Unit: mm)
Service valve
Gas
ø19.05
ø25.4
ø28.58
15