Riello GI/EMME 1400 Manual page 41

Dual fuel light oil/ gas burners
Table of Contents

Advertisement

Boiler
Clean the boiler as indicated in its accompanying instructions in
order to maintain all the original combustion characteristics
intact, especially: the flue gas temperature and combustion
chamber pressure.
Check Mode
With burner flame on:
 hold the reset button on the flame control pressed for at
least 3 sec.;
 the button colour will change from green to yellow;
 each operating status signalling LED will be compared to
20% of the maximum brightness;
 press the reset button again (<0.5sec) to reset the standard
operation of the signalling LEDs.
LIGHT OIL OPERATION
Pump
The delivery pressure must comply with the graph on page 18.
The depression must be less than 0.45 bar.
Unusual noise must not be evident during pump operation.
If the pressure is unstable, or the pump runs noisily, the flexible
hose must be detached from the line filter and the fuel must be
sucked from a tank located near the burner. This measure
permits the cause of the anomaly to be traced to either the
suction piping or the pump. If the problem lies in the suction line,
check the filter is clean and that air is not entering the piping.
Filters
Check the filtering baskets on line and at nozzle present in the
system.
Clean or replace if necessary.
If rust or other impurities are observed inside the pump, use a
separate pump to lift any water and other impurities that may
have deposited on the bottom of the tank.
Nozzles
It is advisable to replace nozzles once a year during periodical
maintenance.
Do not clean the nozzle openings.
Flexible hoses
Check to make sure that the hoses are still in good condition.
Fuel tank
Approximately every 5 years, suck any water on the bottom of the
tank using a separate pump.
Combustion
If the combustion values measured before starting maintenance
do not comply with applicable Standards or do not indicate
efficient combustion, consult the table below or contact our
Technical Support Service to implement the necessary
adjustments.
EN 267
Theoretical max CO
2
0 % O
2
15.2
Air excess
Max. output
Min. output
  1.2
  1.3
CO
% Calibration
2
 = 1.2
 = 1.3
12.6
11.5
Maintenance
Gas leaks
Make sure that there are no gas leaks on the pipe between the
gas meter and the burner.
Gas filter
Change the gas filter when it is dirty.
Combustion
If the combustion values measured before starting maintenance
do not comply with applicable Standards or do not indicate
efficient combustion, consult the table below or contact our
Technical Support Service to implement the necessary
adjustments.
EN 676
Theoretical max
CO
GAS
0 % O
G 20
11.7
G 25
11.5
G 30
14.0
G 31
13.7
7.2.4
Safety components
The safety components should be replaced at the end of their life
cycle indicated in the following table.
ATTENTION
Safety component
Flame control
Flame sensor
Gas valves (solenoid)
Pressure switches
Pressure adjuster
Servomotor (electronic
cam)(if any)
Oil valve (solenoid)(if any)
Oil regulator (if present)
CO
Oil pipes/ couplings
(metallic) (if present)
mg/kWh
Flexible hoses (if present)
 100
Fan impeller
Tab. P
39
GB
GAS OPERATION
Air excess
Max. output
Max. output
  1.2
CO
% Calibration
2
2
 = 1.2
2
9.7
9.5
11.6
11.4
The specified life cycles do not refer to the
warranty terms indicated in the delivery or
payment conditions.
10 years or 250,000
operation cycles
10 years or 250,000
operation cycles
10 years or 250,000
operation cycles
10 years or 250,000
operation cycles
10 years or 250,000
operation cycles
10 years or 250,000
operation cycles
10 years or 250,000
operation cycles
5 years or 30,000 pressurised
10 years or 500,000 start-ups
CO
  1.3
mg/kWh
 = 1.3
 100
9
 100
8.8
 100
10.7
 100
10.5
Tab. Q
Life cycle
15 years
10 years
cycles
Tab. R
20162463